Description

The Honeywell CC-PAON01 (Part Number 51410070-175) is a 16-channel non-HART analog output module engineered for process automation applications within the Honeywell Experion Process Knowledge System (PKS) Series C architecture. Operating on the Series C I/O link (IOLINK) mastered by a C300 controller, the module delivers 4-20 mA control signals to field elements such as control valves, actuators, positioners, and variable speed drives.

Designed as an updated functional successor to earlier CC-PAOX01 and CU-PAOX01 hardware models, the CC-PAON01 utilizes the standard AO16 function block in Experion Control Builder. The module mounts directly onto dedicated Series C Input Output Termination Assemblies (IOTA), integrating into single or redundant IOLINK topographies.

In Experion PKS control architectures, the CC-PAON01 supports both non-redundant and 1-on-1 redundant hardware configurations. Following localized power disruptions, single I/O modules complete initialization in 10 seconds (+/- 25%), resuming control loop processing without requiring full system reboots.

Features

  • Provides 16 analog output channels dedicated to non-HART 4-20 mA field control loops.
  • Interfaces directly with C300 controllers over the Series C I/O link (IOLINK) network.
  • Configured and executed in Experion Control Builder using the standard AO16 IOM block structure.
  • Serves as the direct functional replacement model for legacy CC-PAOX01 and CU-PAOX01 modules.
  • Supports non-redundant (CC-TAON01) and redundant (CC-TAON11) Field Termination Assemblies.
  • Rapid module-level initialization completes within 10 seconds (+/- 25%) following power restoration.
  • Supports up to 40 redundant IOMs per IOLINK and up to 80 redundant IOMs per C300 controller.

Applications

  • Modulating final control elements including 4-20 mA control valves, I/P converters, and positioners.
  • Providing analog control speed references to variable frequency drives (VFD) and motor controllers.
  • Integrating non-HART analog output field loops into Experion PKS C300 process automation systems.

Technical Specifications

Parameter Specification
Manufacturer Honeywell
Model Number CC-PAON01
Part Number 51410070-175
Product Type Series C Non-HART Analog Output Module
Control System Compatibility Experion PKS Series C / C300 Controller
Output Channels 16 channels
Signal Output Type 4-20 mA (Non-HART)
Function Block Type AO16
Compatible Non-Redundant IOTA CC-TAON01
Compatible Redundant IOTA CC-TAON11
System Communication Interface Series C IOLINK
Maximum Modules per IOLINK 40 redundant IOMs
Maximum Modules per C300 Controller 80 redundant IOMs
Single Module Initialization Time 10 seconds (+/- 25%) after module power restoration
Cabinet-Level Initialization Time 60 seconds (+/- 25%) after cabinet power restoration
Superseded Models CC-PAOX01, CU-PAOX01

Connections / Interfaces

Assembly Type Part Number Function
Non-Redundant IOTA CC-TAON01 Single-channel field termination assembly for CC-PAON01
Redundant IOTA CC-TAON11 Dual-channel redundant field termination assembly for CC-PAON01

Installation Guidelines

  1. Verify that the module model (CC-PAON01) and part number (51410070-175) match engineering design drawings before installation.
  2. Confirm cabinet logic power status and observe ESD protection procedures before handling the module assembly.
  3. Align the rear connector of the CC-PAON01 with the designated slot on the CC-TAON01 or CC-TAON11 IOTA base.
  4. Press the module onto the IOTA mounting position until the securing latches click into place.
  5. Inspect field wiring connected to the IOTA screw terminals to ensure secure wire termination and shielding ground connections.

Configuration / Commissioning / Replacement Guidelines

  1. Block Assignment: In Experion Control Builder, assign the channel configuration using the standard AO16 function block.
  2. Link Configuration: Ensure the C300 controller IOLINKTYPE parameter is set correctly to support Series C I/O modules.
  3. Redundancy Restrictions: When replacing older CC-PAOX01 units with CC-PAON01, note that mixed redundant pairs (pairing a PAOX01 with a PAON01) are not supported; online migration requires identical hardware pairs.
  4. Commissioning Verification: Measure loop current across the output terminals using a calibrated meter prior to placing the corresponding control loop into automatic mode.
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
FAQ
What is the primary function of the Honeywell CC-PAON01 51410070-175 module?
The Honeywell CC-PAON01 51410070-175 is a 16-channel analog output module designed to drive 4-20 mA non-HART control loops in Experion PKS Series C systems mastered by C300 controllers.
Is the Honeywell CC-PAON01 module compatible with digital HART communications?
No, the Honeywell CC-PAON01 51410070-175 is strictly a non-HART analog output module. Applications requiring digital HART pass-through must use HART-capable modules such as the CC-PAOH01 or CC-PAOH51.
Which I/O Termination Assemblies (IOTAs) support the CC-PAON01 module?
The Honeywell CC-PAON01 51410070-175 requires the CC-TAON01 IOTA for non-redundant installations or the CC-TAON11 IOTA for redundant module configurations.
Can a Honeywell CC-PAON01 be installed as a redundant partner to an older CC-PAOX01 module?
No, a Honeywell CC-PAON01 cannot form a mixed redundant pair with an older CC-PAOX01 module. Redundant configurations require two identical hardware models on the CC-TAON11 IOTA.
Reviews

CC-PAON01 51410070-175

Stock & lead time on request

Call
1 of 3

Honeywell CC-PAON01 51410070-175 Experion PKS Series C Non-HART Analog Output Module

Only 5 item(s) left in stock
  • Manufacturer: Honeywell

  • Product No.: CC-PAON01 51410070-175

  • Country of origin:United States

  • Product Type: Non-HART Analog Output Modules

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 450g

  • Dimensions: 50 x 120 x 45 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

The Honeywell CC-PAON01 (Part Number 51410070-175) is a 16-channel non-HART analog output module engineered for process automation applications within the Honeywell Experion Process Knowledge System (PKS) Series C architecture. Operating on the Series C I/O link (IOLINK) mastered by a C300 controller, the module delivers 4-20 mA control signals to field elements such as control valves, actuators, positioners, and variable speed drives.

Designed as an updated functional successor to earlier CC-PAOX01 and CU-PAOX01 hardware models, the CC-PAON01 utilizes the standard AO16 function block in Experion Control Builder. The module mounts directly onto dedicated Series C Input Output Termination Assemblies (IOTA), integrating into single or redundant IOLINK topographies.

In Experion PKS control architectures, the CC-PAON01 supports both non-redundant and 1-on-1 redundant hardware configurations. Following localized power disruptions, single I/O modules complete initialization in 10 seconds (+/- 25%), resuming control loop processing without requiring full system reboots.

Features

  • Provides 16 analog output channels dedicated to non-HART 4-20 mA field control loops.
  • Interfaces directly with C300 controllers over the Series C I/O link (IOLINK) network.
  • Configured and executed in Experion Control Builder using the standard AO16 IOM block structure.
  • Serves as the direct functional replacement model for legacy CC-PAOX01 and CU-PAOX01 modules.
  • Supports non-redundant (CC-TAON01) and redundant (CC-TAON11) Field Termination Assemblies.
  • Rapid module-level initialization completes within 10 seconds (+/- 25%) following power restoration.
  • Supports up to 40 redundant IOMs per IOLINK and up to 80 redundant IOMs per C300 controller.

Applications

  • Modulating final control elements including 4-20 mA control valves, I/P converters, and positioners.
  • Providing analog control speed references to variable frequency drives (VFD) and motor controllers.
  • Integrating non-HART analog output field loops into Experion PKS C300 process automation systems.

Technical Specifications

Parameter Specification
Manufacturer Honeywell
Model Number CC-PAON01
Part Number 51410070-175
Product Type Series C Non-HART Analog Output Module
Control System Compatibility Experion PKS Series C / C300 Controller
Output Channels 16 channels
Signal Output Type 4-20 mA (Non-HART)
Function Block Type AO16
Compatible Non-Redundant IOTA CC-TAON01
Compatible Redundant IOTA CC-TAON11
System Communication Interface Series C IOLINK
Maximum Modules per IOLINK 40 redundant IOMs
Maximum Modules per C300 Controller 80 redundant IOMs
Single Module Initialization Time 10 seconds (+/- 25%) after module power restoration
Cabinet-Level Initialization Time 60 seconds (+/- 25%) after cabinet power restoration
Superseded Models CC-PAOX01, CU-PAOX01

Connections / Interfaces

Assembly Type Part Number Function
Non-Redundant IOTA CC-TAON01 Single-channel field termination assembly for CC-PAON01
Redundant IOTA CC-TAON11 Dual-channel redundant field termination assembly for CC-PAON01

Installation Guidelines

  1. Verify that the module model (CC-PAON01) and part number (51410070-175) match engineering design drawings before installation.
  2. Confirm cabinet logic power status and observe ESD protection procedures before handling the module assembly.
  3. Align the rear connector of the CC-PAON01 with the designated slot on the CC-TAON01 or CC-TAON11 IOTA base.
  4. Press the module onto the IOTA mounting position until the securing latches click into place.
  5. Inspect field wiring connected to the IOTA screw terminals to ensure secure wire termination and shielding ground connections.

Configuration / Commissioning / Replacement Guidelines

  1. Block Assignment: In Experion Control Builder, assign the channel configuration using the standard AO16 function block.
  2. Link Configuration: Ensure the C300 controller IOLINKTYPE parameter is set correctly to support Series C I/O modules.
  3. Redundancy Restrictions: When replacing older CC-PAOX01 units with CC-PAON01, note that mixed redundant pairs (pairing a PAOX01 with a PAON01) are not supported; online migration requires identical hardware pairs.
  4. Commissioning Verification: Measure loop current across the output terminals using a calibrated meter prior to placing the corresponding control loop into automatic mode.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell CC-PAON01 51410070-175 Experion PKS Series C Non-HART Analog Output Module

What is the primary function of the Honeywell CC-PAON01 51410070-175 module?

The Honeywell CC-PAON01 51410070-175 is a 16-channel analog output module designed to drive 4-20 mA non-HART control loops in Experion PKS Series C systems mastered by C300 controllers.

Is the Honeywell CC-PAON01 module compatible with digital HART communications?

No, the Honeywell CC-PAON01 51410070-175 is strictly a non-HART analog output module. Applications requiring digital HART pass-through must use HART-capable modules such as the CC-PAOH01 or CC-PAOH51.

Which I/O Termination Assemblies (IOTAs) support the CC-PAON01 module?

The Honeywell CC-PAON01 51410070-175 requires the CC-TAON01 IOTA for non-redundant installations or the CC-TAON11 IOTA for redundant module configurations.

Can a Honeywell CC-PAON01 be installed as a redundant partner to an older CC-PAOX01 module?

No, a Honeywell CC-PAON01 cannot form a mixed redundant pair with an older CC-PAOX01 module. Redundant configurations require two identical hardware models on the CC-TAON11 IOTA.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Black
Country of origin
United States
Power source
DC Power

Recently Viewed Products

Technical knowledge

Implementing 3-Switch XOR Ladder Logic with Internal Bit

Implement a 3-SPST switch XOR light circuit in LogixPro or RSLogix 500 using an internal relay bit. Includes truth tables, boolean equations, and verified.

Building a Modbus RTU Network with CompactLogix and DeltaV

Integrate Allen-Bradley CompactLogix, Caterpillar ATS, and generators into DeltaV DCS over Modbus RTU. Covers ProSoft MVI69-MCM, Miille DIN266 gateways.

ONS Instruction Not Energizing OTE in Studio 5000 Ladder Logic

ONS instruction fires but the OTE coil never latches in Studio 5000 because the one-shot is only true for one scan. Use OTL/OTU or seal-in logic instead.

Kinetix 5500 EtherNet/IP Network Switch Requirements and Topology

Configure Allen-Bradley Kinetix 5500 servo drives on EtherNet/IP. Covers CIP Sync, IEEE 1588 V2 timing, Stratix selection, DLR topology, and HMI.

Moving Average Filtering in DCS and PLC Analog Control

A moving-average filter is the sliding-window smoother most instrument engineers drop into DCS and PLC analog paths. Here is how the window works, how N and sample time set lag, and when a...

GE Mark VI Function Blocks for Gas Turbine Control Logic

On Frame 5–9 gas turbines, GE Mark VI and Mark VIe run control as function-block application software. This article maps process, protection, and sequencing functions—and what Toolbox ST access...