Replacing Yokogawa AAI835: Wiring and Barrier Checks Before Swap
Before replacing a Yokogawa AAI835, verify the 4-in/4-out channel map, power-loss loop behavior, barrier type, output load, cable, and redundancy.
Manufacturer: Honeywell
Product No.: CC-TDI120
Country of origin:United States
Product Type: Digital Input Module
Barcode: 8537101190
Payment: T/T, Western Union
Weight: 400g
Dimensions: 160 x 55 x 120 mm
Shipping port: Xiamen
Warranty: 12 months
The Honeywell CC-PDIH01 is a high-density digital input module designed for process control and monitoring applications within the Experion Series-C I/O platform. It serves as a field interface for high-voltage discrete signals, accepting inputs from field contactors, switches, and interlocks to convey binary system states to the C300 controller.
Featuring 32 input channels, the CC-PDIH01 provides isolated sensing across various high-voltage AC and DC field levels depending on the selected Input Output Termination Assembly (IOTA). By utilizing a universal Input Output Module (IOM) hardware unit paired with specialized high-voltage IOTAs, the module streamlines system spare parts management while delivering galvanically isolated field signal processing for industrial plants.
| Parameter | Specification |
|---|---|
| Manufacturer | Honeywell |
| Model | CC-PDIH01 |
| Product Type | Digital Input High Voltage Module |
| Platform / Family | Experion Series-C I/O |
| Number of Channels | 32 |
| Galvanic Isolation | 1500 VAC RMS or +/-1500 VDC (field to logic common) |
| Isolation Technique | Optical |
| Non-Redundant 120 VAC/125 VDC IOTA | CC-TDI110 (9 inch) |
| Redundant 120 VAC/125 VDC IOTA | CC-TDI120 (12 inch) |
| Non-Redundant 240 VAC IOTA | CC-TDI220 (9 inch) |
| Redundant 240 VAC IOTA | CC-TDI230 (12 inch) |
| 120 VAC Operating Voltage Range | 90 to 132 VAC RMS |
| 125 VDC Operating Voltage Range | 100 to 138 VDC |
| 240 VAC Operating Voltage Range | 180 to 264 VAC RMS |
| Line Frequency Range | 47 to 63 Hz |
| 120 VAC Sense Current (ON) | 7.5 mA RMS min @ 90V RMS; 10 mA RMS @ 132V RMS |
| 125 VDC Sense Current (ON) | 1.2 mA min |
| 240 VAC Sense Current (ON) | 1.11 mA RMS min |
| 120 VAC Sense Current (OFF) | 2.0 mA RMS max |
| 125 VDC / 240 VAC Sense Current (OFF) | 0.32 mA / 0.32 mA RMS max |
| 120 VAC Pick-Up Voltage (ON) | 90 VAC RMS min |
| 125 VDC Pick-Up Voltage (ON) | 100 VDC min |
| 240 VAC Pick-Up Voltage (ON) | 180 VAC RMS min |
| Drop-Out Voltage (OFF Max) | 20 VAC RMS (120V) / 25 VDC (125V) / 50 VAC RMS (240V) |
| Input Delay / Response Time | 25 ms max (120/240 VAC); 10 ms max (125 VDC) |
| IOTA Model | Voltage Application | Configuration Type | Board Size |
|---|---|---|---|
| CC-TDI110 | 120 VAC / 125 VDC | Non-Redundant | 9 inch |
| CC-TDI120 | 120 VAC / 125 VDC | Redundant | 12 inch |
| CC-TDI220 | 240 VAC | Non-Redundant | 9 inch |
| CC-TDI230 | 240 VAC | Redundant | 12 inch |
Global Express Shipping
Returns & Warranty



Global Express Shipping
Returns & Warranty
Orders are processed and delivered Monday-Friday (excluding public holidays).
For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .
| Color pattern |
Black
|
| Country of origin |
United States
|
| Power source |
DC Power
AC-powered
|