Honeywell

Honeywell FC-CPCHAS-0001 Safety Manager Controller Chassis

SKU FC-CPCHAS-0001

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Honeywell

  • Product No.: FC-CPCHAS-0001

  • Country of origin:United States

  • Product Type: Controller Chassis

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 5800g

  • Dimensions: 482.6 mm x 177 mm x 280 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The Honeywell FC-CPCHAS-0001 is a 19-inch rack-mounted Controller Chassis engineered to house and interface the Control Processor modules within the Honeywell Safety Manager system architecture. Installed as the main processing enclosure at the top position of a system cabinet, it provides structural housing and complete backplane interconnection for both redundant and non-redundant Safety Manager controller configurations.

The chassis integrates a specialized controller housing with card guides, quarter-turn module locks, and a integrated controller backplane (CPB-0001). The rear section features a magnetically locked back cover plate that swings upward to expose signal connections and a structured cable-management framework with dedicated horizontal bars for 24 Vdc supply/signals, communication links, and 5V/Watchdog lines. The unit routes internal power distribution—including a diode-decoupled, redundant 5V supply (5V-R) derived from connected power supply units—and interfaces up to four I/O buses, watchdog outputs, system power, and communication lines to field I/O racks and external networks.

Features

  • Dual-Configuration Flexibility: Supports both single (non-redundant) and fault-tolerant redundant Control Processor setups within a single standard 19-inch housing.
  • Integrated Backplane Architecture: Incorporates the CPB-0001 controller backplane to deliver signal routing, 5V-R diode-decoupled redundant power distribution, and I/O bus connections.
  • Structured Rear Cable Management: Features three dedicated horizontal tie-wrap bars to separate 24 Vdc power/signals, communication cables, and low-voltage 5V/watchdog cabling.
  • Swing-Up Rear Protection: Magnetically locked rear cover plate swings upward for easy access to backplane connectors during installation and maintenance.
  • Comprehensive Expansion Capability: Offers interfaces for up to 4 I/O buses with dedicated terminator sockets (TERM-0001/TERM-0002) and 8 watchdog/power distribution channels (WdP1–WdP8) for downstream I/O chassis connection.
  • Dedicated Control Inputs: Includes external Emergency Shut Down (SD) interlock terminals and 3 non-safety 24 Vdc general-purpose inputs (IN1–IN3) for functions such as external clock synchronization.

Applications

  • Safety Manager Main Controller Enclosure: Primary processing hub housing Quad Processor Packs (QPP-0002), Universal Safety Interfaces (USI-0002 / FX-USI-0002), Power Supplies (PSU-240516), and Battery & Key Switch Modules (BKM-0001).
  • Emergency Shutdown (ESD) Systems: Core chassis housing for ESD logic solvers in process plants, offshore platforms, and refineries.
  • Burner Management Systems (BMS) & Fire & Gas (F&G): Central hardware frame for processing high-integrity safety loops and fire/gas monitoring logic.

Technical Specifications

General

Parameter Specification
Manufacturer Honeywell
Exact Model FC-CPCHAS-0001
Type Number FS-CPCHAS-0001
Product Type Controller Chassis
Frame / Mounting Standard 19-inch Rack Cabinet Mount (4 HE)
Power Consumption (5V-1) 0.05 A
Power Consumption (5V-2) 0.05 A

Slot & Module Capacity

Parameter Specification
Primary Processor Slots CPU1 (QPP-0002), CPU2 (QPP-0002, optional for redundancy)
Communication Slots COM1.1, COM1.2, COM2.1, COM2.2 (USI-0002 / FX-USI-0002 or BLIND-COM)
Power Supply Slots PSU1 (PSU-240516), PSU2 (PSU-240516, optional for redundancy)
Shared Module Slot BKM (BKM-0001 Battery and Key Switch Module)
Unused Slot Cover Plate BLIND-CPS (for non-redundant CPU/PSU slots)

Mechanical & Environmental

Parameter Specification
Height 4 HE (177 mm / 7 in)
Width 482.6 mm / 19 in
Depth 280 mm / 11 in
Net Weight 5.8 kg / 12.8 lb
Rear Cover Locking Magnetic lock mechanism

Connections / Interfaces

Connector Group Connector Type Function
COM1.1.A / B, COM1.2.A / B RJ45 Ethernet communication channels 1 and 2 for CP1 modules
COM1.1.C / D, COM1.2.C / D 10-pin male General purpose communication channels 3 and 4 for CP1 modules
COM2.1.A / B, COM2.2.A / B RJ45 Ethernet communication channels 1 and 2 for CP2 modules
COM2.1.C / D, COM2.2.C / D 10-pin male General purpose communication channels 3 and 4 for CP2 modules
IO bus 1 to 4 (1.1–1.4 & 2.1–2.4) Flat cable connectors I/O bus interface links for Control Processor 1 and Control Processor 2
Term IO bus 1 to 4 2 x 50-pin connector Sockets for IO bus terminators (TERM-0001 or TERM-0002)
WdP1 to WdP8 8-pin male Watchdog and Power distribution connectors to I/O chassis 1 through 8
24V-1 / 24V-2 2-pin male Main +24V power supply inputs for CP1 and CP2
5V-1 / 5V-2 / 5V-R 4-pin male 5V and Watchdog distribution to extension cabinets via PDB-IOX05
SD 2-pin male Emergency Shut Down loop input (shunted via LINK-SD if unused)
IN1, IN2, IN3 2-pin male 24V non-safety general purpose inputs (IN1 supports clock sync interrupt)

Installation Guidelines

  1. Rack Mounting: Install the Honeywell FC-CPCHAS-0001 horizontally into a standard 19-inch rack cabinet, typically positioned at the top location above the associated I/O chassis.
  2. Grounding Verification: Ensure the chassis is bonded to the main cabinet frame ground. Built-in keying pins in the backplane provide chassis ground connection to module housings.
  3. Module Insertion: Insert modules (QPP-0002, USI-0002, PSU-240516, BKM-0001) along the top and bottom guide rails through the front opening. Secure each module by tightening the quarter-turn fasteners below the module grips.
  4. Blanking Plates: Fit BLIND-CPS plates over unused processor/power supply slots and BLIND-COM plates over unused communication slots to prevent airflow bypass and contamination.
  5. Rear Cable Management: Swing open the rear magnetic cover plate. Group and secure cables to the horizontal tie-wrap bars according to voltage levels:
    • Top Bar: 24 Vdc supply and 24 Vdc signal wiring.
    • Middle Bar: System Ethernet and general-purpose communication cables.
    • Bottom Bar: 5V auxiliary and Watchdog distribution cables.
  6. I/O Bus Termination: Verify that appropriate bus terminators (TERM-0001 or TERM-0002) are fully seated in all active Term IO bus sockets on the rear backplane.
  7. Emergency Shutdown Link: Ensure the factory-installed LINK-SD jumper remains connected across the SD terminals unless an external hardwired Emergency Shut Down contact is wired to the chassis.

Configuration and Commissioning Recommendations

  1. Power Supply Redundancy Check: Measure voltage at 5V-1, 5V-2, and 5V-R backplane test terminals. Confirm that 5V-R remains energized when either power supply module (PSU1 or PSU2) is operational.
  2. Communication Verification: Verify link activity on RJ45 ports (COM1.1–COM2.2) when connected to system switches or downstream Safety Manager networks.
  3. Interrupt & Clock Sync Verification: If using IN1 for clock synchronization, verify rising-edge signal integrity and line voltage levels before enabling software interrupts.

Compliance and Certifications

  • CE: European Conformity
  • UL: Underwriters Laboratories
  • CSA: Canadian Standards Association
  • TUV: TÜV Certified for Functional Safety
  • FM: Factory Mutual Approved

FAQ

What is the function of the Honeywell FC-CPCHAS-0001 chassis?

The Honeywell FC-CPCHAS-0001 serves as the central 19-inch 4HE enclosure housing Control Processor modules, power supplies, communication interfaces, and the CPB-0001 backplane for Honeywell Safety Manager systems.

Does the Honeywell FC-CPCHAS-0001 support redundant controller configurations?

Yes, the Honeywell FC-CPCHAS-0001 accommodates both non-redundant and dual-redundant Control Processor setups, providing dedicated CPU, COM, and PSU module slots alongside a shared BKM-0001 module position.

How is power redundancy managed within the Honeywell FC-CPCHAS-0001 backplane?

The integrated CPB-0001 backplane combines and diode-decouples the 5V power supply outputs from both PSU modules to form a redundant 5V-R line, ensuring continuous operation for non-redundant I/O if one supply fails.

What I/O bus termination modules are used with the Honeywell FC-CPCHAS-0001?

The rear backplane of the Honeywell FC-CPCHAS-0001 includes sockets for up to four I/O bus connections, which require TERM-0001 or TERM-0002 bus terminators installed into the corresponding Term IO bus sockets.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell FC-CPCHAS-0001 Safety Manager Controller Chassis

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 4
Only 7 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Technical knowledge

Replacing Yokogawa AAI835: Wiring and Barrier Checks Before Swap

Before replacing a Yokogawa AAI835, verify the 4-in/4-out channel map, power-loss loop behavior, barrier type, output load, cable, and redundancy.

ABB PM891K01 Replacement: Check Redundancy Before Ordering

ABB PM891K01 article 3BSE053241R1 is the non-redundant AC 800M processor kit. Use this field checklist before replacement.

ABB TP853 Replacement Checks for CI853/CI855/CI857/CI861

Replacement checks for ABB TP853 3BSE018126R1: identify the installed CI853, CI855, CI857, or CI861 interface, record wiring, and verify communication after installation.

5069-L330ERMS2 Startup Checks: RTBs, I/O, and Motion Limits

Engineering checks for the Allen-Bradley 5069-L330ERMS2: controller capacity, separate RTB kits, local I/O limits, network-node limits, and motion-axis count.

Replacing ABB DSQC 351: Controller and Network Checks

Checks to record before replacing ABB 3HNE 00006-1 DSQC 351: controller generation, X3/X5/X20/X21 wiring, DeviceNet settings, INTERBUS mapping, and LED states.

IC693CPU360 vs IC693CPU364: Ethernet and Power Budget

Compare the IC693CPU360 and IC693CPU364 by Ethernet interface, +5 VDC load, memory, rack limits, and replacement checks.