Honeywell

Honeywell FS-SDO-0824 Safety Manager Safe Digital Output Module

SKU FS-SDO-0824

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Honeywell
  • Product No.: FS-SDO-0824
  • Origin United States
  • Product Type: Safe Digital Output Module
  • Barcode: 8537101190
  • Payment: T/T, Western Union
  • Weight: 3.0 kg
  • Dimensions: 250 x 30 x 220 mm
  • Shipping port: Xiamen
  • Warranty: 12 months

Tags

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell FS-SDO-0824 Safety Manager Safe Digital Output Module

Quantity

Product Description

Description

The Honeywell FS-SDO-0824 is a non-conformal coated safe digital output module engineered for critical process control, safety instrumented systems (SIS), and emergency shutdown (ESD) applications within the Honeywell Safety Manager platform. Operating as a high-integrity logic solver interface, the module acts as a key execution unit within Safety Instrumented Functions (SIFs) up to SIL3 compliance levels. It converts internal logic commands from the controller chassis into field-level electrical signals, allowing precise, fail-safe driving of safety-critical field actuators, solenoid valves, interposing relays, and alarm indication equipment.

Constructed specifically for integration into Safety Manager IO chassis (such as IOCHAS-0001S/R or IOCHAS-0002S/R), the FS-SDO-0824 utilizes an 8-channel solid-state sourcing topology. Each output channel delivers a regulated 24 Vdc supply capable of sourcing up to 550 mA per point, designed with built-in short-circuit protection and internal fault diagnostics to prevent dangerous undetected failures. The non-conformal coated design (designated by the FS- prefix) is optimized for standard control room environments, cabinet enclosures, and temperature-controlled industrial automation centers.

The module architecture integrates multi-stage internal power rails to separate system logic processing from field loop current delivery. Internal logic circuits draw power directly from a 5 Vdc supply rail and a 24 Vdc internal bus, while output field loops are powered through a dedicated 24 Vdc external supply rail. Integrated watchdog (WDG) monitoring actively validates system logic health and control signals before permitting output state changes, assuring immediate fail-safe trip action in the event of an upstream system fault.

To maintain hardware integrity during system assembly and field servicing, the FS-SDO-0824 incorporates physical key coding mechanisms. Rear edge-connector key coding prevents cross-insertion into incorrect IO chassis slots, protecting both the module logic board and connected field instrumentation from incorrect voltage exposure. The module interfaces seamlessly with dedicated Field Termination Assemblies (such as TSDO-0824 or TSDO-0824C) via system interconnection cables, simplifying cabinet wiring and maintenance.

Features

  • Fail-Safe Solid-State Outputs: Features 8 independent 24 Vdc sourcing channels equipped with short-circuit protection for high-availability safety applications.
  • Integrated Watchdog Supervision: Incorporates dedicated watchdog input signal circuitry (8 mA rating) to monitor logic execution state and trigger fail-safe actions.
  • Separated Power Architecture: Isolates internal logic processing (5 Vdc and 24 Vdc internal) from external field load power (24 Vdc external) to minimize electrical noise propagation.
  • Mechanical Key Coding Security: Utilizes predefined rear connector coding pin configurations (A9/C9) to prevent incorrect module insertion into IO chassis slots.
  • High Load Capacity Handling: Capable of driving resistive, inductive, capacitive (up to 1 µF), and incandescent lamp loads (up to 120 mA / 2.9 W) directly.
  • Comprehensive Fault Diagnostics: Built-in current limiting and low off-state leakage (< 0.1 mA) safeguard connected actuators against unintended activation or thermal stress.
  • Non-Conformal Coated Construction: Form-fit for standard industrial control cabinets, process control rooms, and clean automation enclosures.

Applications

  • Emergency Shutdown Systems (ESD): Direct control of 24 Vdc de-energize-to-trip solenoid valves, isolation valves, and emergency shutoff actuators.
  • Fire and Gas Safety Systems (F&G): Driving field visual beacons, alarm horns, suppression release solenoids, and local status indicators.
  • Burner Management Systems (BMS): Safe output control for fuel gas safety shutoff valves, ignition sequence relays, and purge interlocks.
  • High-Integrity Pressure Protection Systems (HIPPS): High-speed tripping of fast-acting safety isolation valves in high-pressure gas or fluid pipelines.
  • Interposing Relay Interfaces: Switching higher-power field loads, motor control center (MCC) starter circuits, and auxiliary control loops through safe interposing relays.

Technical Specifications

General

Parameter Specification
Manufacturer Honeywell
Model FS-SDO-0824 V1.2
Product Type Safe Digital Output Module
Coating Type Non-Conformal Coated (FS-Type)
Safety Integrity Level SIL1 to SIL3 (System Level)
Number of Output Channels 8
Key Coding Positions Module Holes: A9, C9 / Chassis Pins: A9, C9
System Interconnection System Interconnection Cables (SICC) to TSDO-0824 / TSDO-0824C FTAs

Power Requirements

Parameter Specification
5 Vdc Power Supply Rail 5 Vdc, 25 mA
Internal 24 Vdc Power Supply Rail 24 Vdc, 25 mA
External 24 Vdc Power Supply Rail 24 Vdc, 70 mA (without output load)
Operating Voltage Range (24 Vdc) 20.4 Vdc to 31.2 Vdc (+30% / -15%)

Output Ratings & Performance

Parameter Specification
Output Type 24 Vdc solid-state source, short-circuit proof
Maximum Output Current 550 mA per channel
Maximum Voltage Drop < 2.0 Vdc at 500 mA
Off-State Leakage Current < 0.1 mA
Maximum Lamp Load 120 mA (2.9 W)
Maximum Load Capacitance 1 µF
Watchdog (WDG) Input Current 8 mA

Environmental & Operating Conditions

Parameter Specification
Operating Temperature (Cabinet) -5 degC to 70 degC (23 degF to 158 degF)
Storage Temperature -40 degC to 85 degC (-40 degF to 185 degF)
Relative Humidity 5% to 95% (non-condensing)
Sinusoidal Vibration 10 Hz to 57 Hz: 0.075 mm amplitude; 57 Hz to 150 Hz: 1 G (3 axes)
Mechanical Shock Resistance 15 G, 11 ms duration, half-sine (3 axes)

Installation Guidelines

  1. Pre-Installation Safety Inspection: Unpack the module inside an Electrostatic Discharge (ESD) safe area. Inspect the module rear connector pins, housing latching mechanisms, and front cable guide for physical transport damage.
  2. Verify Slot Key Coding: Ensure the destination IO chassis slot is fitted with correct Souriau key coding pins at positions A9 and C9. Do not attempt to force a module into a slot with mismatched key coding.
  3. Power Isolation Checks: De-energize or disconnect external 24 Vdc power feeds to the corresponding Field Termination Assembly (FTA) prior to making wiring or hardware changes.
  4. Module Insertion: Align the printed circuit board card edges with the card guide rails inside the IO chassis. Firmly slide the module inward until the rear edge-connector seats completely into the backplane socket.
  5. Bus Cable Connection: Securely attach the module's front flat cable connector to the IO chassis front bus print header. Ensure all strain relief tabs engage correctly.
  6. Grounding & Shielding: Confirm system cabinet protective earth (PE) ground connections and ensure field cable shielding is terminated according to Safety Manager installation specifications.

Configuration Guidelines

  1. Hardware Configurator Setup: Open the Honeywell Safety Builder software and add the FS-SDO-0824 module to the corresponding IO chassis slot within the system configuration tree.
  2. Channel Parameterization: Configure each of the 8 output channels according to loop requirements (e.g., de-energize-to-trip or energize-to-trip logic execution rules).
  3. Tag Assignment: Assign functional safety tag names, application logic linkages, and alarm configuration limits to each channel point within Safety Builder.
  4. Logic Downloader Application: Compile and download the updated Safety Builder project configuration to the Control Processor (QPP) modules.

Commissioning & Replacement Recommendations

  • Pre-Commissioning Voltage Checks: Verify that the external 24 Vdc supply fed to the field termination assembly stays strictly within the 20.4 Vdc to 31.2 Vdc operating threshold under full load conditions.
  • Output Channel Functional Test: Measure the output voltage across field terminal terminals when commanding channels ON (24 Vdc nominal) and OFF (< 2.0 Vdc drop check).
  • Hot-Swapping / Online Module Replacement: If replacing an existing module during active operation, ensure system redundancy requirements and safety interlocks allow safe online module exchange according to plant safety procedures.
  • Spare Module Storage: Store spare non-conformal coated modules in antistatic packaging within sealed, dry storage environments (-40 degC to 85 degC).
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
FAQ
What is the primary function of the Honeywell FS-SDO-0824 module?
The module serves as an 8-channel safe digital output interface within Honeywell Safety Manager systems. It receives logic commands from the central control processor and safely drives external 24 Vdc field actuators, solenoids, and indicators in Safety Instrumented Functions (SIFs).
What does the FS prefix indicate on the FS-SDO-0824 module?
The FS prefix designates that the module is non-conformal coated, suitable for standard indoor control rooms and protected enclosure cabinets. Conformal coated versions of Safety Manager hardware typically carry an FC prefix.
What are the power requirements for the FS-SDO-0824 module?
The module requires three distinct power rails: a 5 Vdc supply at 25 mA for internal logic, an internal 24 Vdc supply at 25 mA, and an external 24 Vdc supply rail at 70 mA (unloaded) to power field output sourcing circuits.
What physical key coding configuration does the FS-SDO-0824 output module use?
The module utilizes Souriau 5159 key coding with pin positions A9 and C9 in the chassis connector corresponding to matching hole positions on the module connector. This prevents accidental insertion into incorrect IO chassis slots.
How many channels does the FS-SDO-0824 provide and what is the current rating per point?
The module provides 8 solid-state sourcing output channels. Each individual channel can deliver a maximum output current of up to 550 mA at 24 Vdc, featuring short-circuit protection and low off-state leakage.
Reviews

FS-SDO-0824

Stock &amp; lead time on request

Call
1 of 4

Honeywell FS-SDO-0824 Safety Manager Safe Digital Output Module

Only 8 item(s) left in stock
  • Manufacturer: Honeywell

  • Product No.: FS-SDO-0824

  • Country of origin:United States

  • Product Type: Safe Digital Output Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 3000g

  • Dimensions: 250 x 30 x 220 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

The Honeywell FS-SDO-0824 is a non-conformal coated safe digital output module engineered for critical process control, safety instrumented systems (SIS), and emergency shutdown (ESD) applications within the Honeywell Safety Manager platform. Operating as a high-integrity logic solver interface, the module acts as a key execution unit within Safety Instrumented Functions (SIFs) up to SIL3 compliance levels. It converts internal logic commands from the controller chassis into field-level electrical signals, allowing precise, fail-safe driving of safety-critical field actuators, solenoid valves, interposing relays, and alarm indication equipment.

Constructed specifically for integration into Safety Manager IO chassis (such as IOCHAS-0001S/R or IOCHAS-0002S/R), the FS-SDO-0824 utilizes an 8-channel solid-state sourcing topology. Each output channel delivers a regulated 24 Vdc supply capable of sourcing up to 550 mA per point, designed with built-in short-circuit protection and internal fault diagnostics to prevent dangerous undetected failures. The non-conformal coated design (designated by the FS- prefix) is optimized for standard control room environments, cabinet enclosures, and temperature-controlled industrial automation centers.

The module architecture integrates multi-stage internal power rails to separate system logic processing from field loop current delivery. Internal logic circuits draw power directly from a 5 Vdc supply rail and a 24 Vdc internal bus, while output field loops are powered through a dedicated 24 Vdc external supply rail. Integrated watchdog (WDG) monitoring actively validates system logic health and control signals before permitting output state changes, assuring immediate fail-safe trip action in the event of an upstream system fault.

To maintain hardware integrity during system assembly and field servicing, the FS-SDO-0824 incorporates physical key coding mechanisms. Rear edge-connector key coding prevents cross-insertion into incorrect IO chassis slots, protecting both the module logic board and connected field instrumentation from incorrect voltage exposure. The module interfaces seamlessly with dedicated Field Termination Assemblies (such as TSDO-0824 or TSDO-0824C) via system interconnection cables, simplifying cabinet wiring and maintenance.

Features

  • Fail-Safe Solid-State Outputs: Features 8 independent 24 Vdc sourcing channels equipped with short-circuit protection for high-availability safety applications.
  • Integrated Watchdog Supervision: Incorporates dedicated watchdog input signal circuitry (8 mA rating) to monitor logic execution state and trigger fail-safe actions.
  • Separated Power Architecture: Isolates internal logic processing (5 Vdc and 24 Vdc internal) from external field load power (24 Vdc external) to minimize electrical noise propagation.
  • Mechanical Key Coding Security: Utilizes predefined rear connector coding pin configurations (A9/C9) to prevent incorrect module insertion into IO chassis slots.
  • High Load Capacity Handling: Capable of driving resistive, inductive, capacitive (up to 1 µF), and incandescent lamp loads (up to 120 mA / 2.9 W) directly.
  • Comprehensive Fault Diagnostics: Built-in current limiting and low off-state leakage (< 0.1 mA) safeguard connected actuators against unintended activation or thermal stress.
  • Non-Conformal Coated Construction: Form-fit for standard industrial control cabinets, process control rooms, and clean automation enclosures.

Applications

  • Emergency Shutdown Systems (ESD): Direct control of 24 Vdc de-energize-to-trip solenoid valves, isolation valves, and emergency shutoff actuators.
  • Fire and Gas Safety Systems (F&G): Driving field visual beacons, alarm horns, suppression release solenoids, and local status indicators.
  • Burner Management Systems (BMS): Safe output control for fuel gas safety shutoff valves, ignition sequence relays, and purge interlocks.
  • High-Integrity Pressure Protection Systems (HIPPS): High-speed tripping of fast-acting safety isolation valves in high-pressure gas or fluid pipelines.
  • Interposing Relay Interfaces: Switching higher-power field loads, motor control center (MCC) starter circuits, and auxiliary control loops through safe interposing relays.

Technical Specifications

General

Parameter Specification
Manufacturer Honeywell
Model FS-SDO-0824 V1.2
Product Type Safe Digital Output Module
Coating Type Non-Conformal Coated (FS-Type)
Safety Integrity Level SIL1 to SIL3 (System Level)
Number of Output Channels 8
Key Coding Positions Module Holes: A9, C9 / Chassis Pins: A9, C9
System Interconnection System Interconnection Cables (SICC) to TSDO-0824 / TSDO-0824C FTAs

Power Requirements

Parameter Specification
5 Vdc Power Supply Rail 5 Vdc, 25 mA
Internal 24 Vdc Power Supply Rail 24 Vdc, 25 mA
External 24 Vdc Power Supply Rail 24 Vdc, 70 mA (without output load)
Operating Voltage Range (24 Vdc) 20.4 Vdc to 31.2 Vdc (+30% / -15%)

Output Ratings & Performance

Parameter Specification
Output Type 24 Vdc solid-state source, short-circuit proof
Maximum Output Current 550 mA per channel
Maximum Voltage Drop < 2.0 Vdc at 500 mA
Off-State Leakage Current < 0.1 mA
Maximum Lamp Load 120 mA (2.9 W)
Maximum Load Capacitance 1 µF
Watchdog (WDG) Input Current 8 mA

Environmental & Operating Conditions

Parameter Specification
Operating Temperature (Cabinet) -5 degC to 70 degC (23 degF to 158 degF)
Storage Temperature -40 degC to 85 degC (-40 degF to 185 degF)
Relative Humidity 5% to 95% (non-condensing)
Sinusoidal Vibration 10 Hz to 57 Hz: 0.075 mm amplitude; 57 Hz to 150 Hz: 1 G (3 axes)
Mechanical Shock Resistance 15 G, 11 ms duration, half-sine (3 axes)

Installation Guidelines

  1. Pre-Installation Safety Inspection: Unpack the module inside an Electrostatic Discharge (ESD) safe area. Inspect the module rear connector pins, housing latching mechanisms, and front cable guide for physical transport damage.
  2. Verify Slot Key Coding: Ensure the destination IO chassis slot is fitted with correct Souriau key coding pins at positions A9 and C9. Do not attempt to force a module into a slot with mismatched key coding.
  3. Power Isolation Checks: De-energize or disconnect external 24 Vdc power feeds to the corresponding Field Termination Assembly (FTA) prior to making wiring or hardware changes.
  4. Module Insertion: Align the printed circuit board card edges with the card guide rails inside the IO chassis. Firmly slide the module inward until the rear edge-connector seats completely into the backplane socket.
  5. Bus Cable Connection: Securely attach the module's front flat cable connector to the IO chassis front bus print header. Ensure all strain relief tabs engage correctly.
  6. Grounding & Shielding: Confirm system cabinet protective earth (PE) ground connections and ensure field cable shielding is terminated according to Safety Manager installation specifications.

Configuration Guidelines

  1. Hardware Configurator Setup: Open the Honeywell Safety Builder software and add the FS-SDO-0824 module to the corresponding IO chassis slot within the system configuration tree.
  2. Channel Parameterization: Configure each of the 8 output channels according to loop requirements (e.g., de-energize-to-trip or energize-to-trip logic execution rules).
  3. Tag Assignment: Assign functional safety tag names, application logic linkages, and alarm configuration limits to each channel point within Safety Builder.
  4. Logic Downloader Application: Compile and download the updated Safety Builder project configuration to the Control Processor (QPP) modules.

Commissioning & Replacement Recommendations

  • Pre-Commissioning Voltage Checks: Verify that the external 24 Vdc supply fed to the field termination assembly stays strictly within the 20.4 Vdc to 31.2 Vdc operating threshold under full load conditions.
  • Output Channel Functional Test: Measure the output voltage across field terminal terminals when commanding channels ON (24 Vdc nominal) and OFF (< 2.0 Vdc drop check).
  • Hot-Swapping / Online Module Replacement: If replacing an existing module during active operation, ensure system redundancy requirements and safety interlocks allow safe online module exchange according to plant safety procedures.
  • Spare Module Storage: Store spare non-conformal coated modules in antistatic packaging within sealed, dry storage environments (-40 degC to 85 degC).
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell FS-SDO-0824 Safety Manager Safe Digital Output Module

What is the primary function of the Honeywell FS-SDO-0824 module?

The module serves as an 8-channel safe digital output interface within Honeywell Safety Manager systems. It receives logic commands from the central control processor and safely drives external 24 Vdc field actuators, solenoids, and indicators in Safety Instrumented Functions (SIFs).

What does the FS prefix indicate on the FS-SDO-0824 module?

The FS prefix designates that the module is non-conformal coated, suitable for standard indoor control rooms and protected enclosure cabinets. Conformal coated versions of Safety Manager hardware typically carry an FC prefix.

What are the power requirements for the FS-SDO-0824 module?

The module requires three distinct power rails: a 5 Vdc supply at 25 mA for internal logic, an internal 24 Vdc supply at 25 mA, and an external 24 Vdc supply rail at 70 mA (unloaded) to power field output sourcing circuits.

What physical key coding configuration does the FS-SDO-0824 output module use?

The module utilizes Souriau 5159 key coding with pin positions A9 and C9 in the chassis connector corresponding to matching hole positions on the module connector. This prevents accidental insertion into incorrect IO chassis slots.

How many channels does the FS-SDO-0824 provide and what is the current rating per point?

The module provides 8 solid-state sourcing output channels. Each individual channel can deliver a maximum output current of up to 550 mA at 24 Vdc, featuring short-circuit protection and low off-state leakage.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Blue
Country of origin
United States
Power source
AC-powered

Recently Viewed Products

Technical knowledge

Implementing 3-Switch XOR Ladder Logic with Internal Bit

Implement a 3-SPST switch XOR light circuit in LogixPro or RSLogix 500 using an internal relay bit. Includes truth tables, boolean equations, and verified.

Building a Modbus RTU Network with CompactLogix and DeltaV

Integrate Allen-Bradley CompactLogix, Caterpillar ATS, and generators into DeltaV DCS over Modbus RTU. Covers ProSoft MVI69-MCM, Miille DIN266 gateways.

ONS Instruction Not Energizing OTE in Studio 5000 Ladder Logic

ONS instruction fires but the OTE coil never latches in Studio 5000 because the one-shot is only true for one scan. Use OTL/OTU or seal-in logic instead.

Kinetix 5500 EtherNet/IP Network Switch Requirements and Topology

Configure Allen-Bradley Kinetix 5500 servo drives on EtherNet/IP. Covers CIP Sync, IEEE 1588 V2 timing, Stratix selection, DLR topology, and HMI.

Moving Average Filtering in DCS and PLC Analog Control

A moving-average filter is the sliding-window smoother most instrument engineers drop into DCS and PLC analog paths. Here is how the window works, how N and sample time set lag, and when a...

GE Mark VI Function Blocks for Gas Turbine Control Logic

On Frame 5–9 gas turbines, GE Mark VI and Mark VIe run control as function-block application software. This article maps process, protection, and sequencing functions—and what Toolbox ST access...