Honeywell TK-FFIF01 51403420-275 Experion PKS CIOM-A Fieldbus Interface Module

Honeywell TK-FFIF01 51403420-275 Experion PKS CIOM-A Fieldbus Interface Module

Only 2 item(s) left in stock
  • Manufacturer: Honeywell

  • Product No.: TK-FFIF01 51403420-275

  • Country of origin:United States

  • Product Type: Fieldbus Interface Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 850g

  • Dimensions: 140 mm x 250 mm x 130 mm (H x W x D)

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

The Honeywell TK-FFIF01 (part number 51403420-275) is a conformally coated CIOM-A Fieldbus Interface Module (FIM2) designed for the Experion Process Knowledge System (PKS). The TK-FFIF01 double-width chassis-based module installs directly into an Experion C200 Controller rack or a remote I/O chassis rack to deliver high-capacity FOUNDATION Fieldbus integration. It supports two (2) H1 Fieldbus networks running at 31.25 kbps, enabling transparent, system-wide access to device data, control signals, diagnostics, and alarms without single points of failure.

Features

  • Double slot-width module design compatible with Experion C200 Controller racks and remote I/O chassis racks.
  • Supports two (2) H1 FOUNDATION Fieldbus networks operating at 31.25 kbps.
  • High-capacity architecture providing direct integration of data access, control, connections, diagnostics, and alarms.
  • Conformal coating protection for enhanced durability in harsh industrial operating environments.
  • Full support for Link Active Schedule (LAS) and Backup LAS capabilities to maintain link availability during module disruption or removal.
  • Compatible with non-redundant and redundant configurations using the Redundancy Module (RM).

Applications

  • Experion PKS C200 Controller system integration
  • Process automation in chemical plants, oil and gas refineries, and offshore/onshore platforms
  • Power generation boilers and pilot plant operations
  • Pharmaceutical and advanced manufacturing fieldbus device networks

Technical Specifications

Parameter Specification
Manufacturer Honeywell
Model TK-FFIF01
Part Number 51403420-275
Module Type Double slot-width module (CIOM-A)
Coating Conformally coated
Physical Interface H1 FOUNDATION Fieldbus
Number of H1 Networks per FIM 2 (each running at 31.25 kbps)
Maximum Fieldbus Devices per H1 Network 16
Available Macrocycle Period 250 ms, 500 ms, 1 sec, 2 sec, 4 sec, 8 sec, 16 sec, 32 sec
Module Connection to RTP TC-FFCxxx Fieldbus RTP Cable

Connections/Interfaces

Connector / Interface Function
Chassis Slot Interface Double slot-width rack backplane bus connection to C200 Controller or Remote I/O chassis
RTP Interface Connector Dedicated connection to Fieldbus Remote Termination Panels via TC-FFCxxx cables
H1 Fieldbus Link 1 Primary/Secondary H1 Fieldbus network segment 1 connection
H1 Fieldbus Link 2 Primary/Secondary H1 Fieldbus network segment 2 connection

Installation Guidelines

  • Rack Mounting: Ensure the module is properly aligned and seated into two adjacent chassis slots within the Experion C200 Controller rack or remote I/O chassis rack.
  • Cable Routing: Connect the module to the appropriate Remote Termination Panel (RTP) using official TC-FFCxxx series Fieldbus RTP cables (e.g., TC-FFC010, TC-FFC025, TC-FFC050, or TC-FFC100).
  • Grounding & Shielding: Maintain proper fieldbus cable shielding and system grounding to mitigate EMI/RFI interference on the 31.25 kbps H1 communication links.
  • Redundancy Setup: For redundant operation, ensure synchronization is configured via the Redundancy Module (RM) according to Experion PKS guidelines.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell TK-FFIF01 51403420-275 Experion PKS CIOM-A Fieldbus Interface Module

How many H1 Fieldbus networks are supported by the module?

The module supports two (2) H1 FOUNDATION Fieldbus networks running at 31.25 kbps.

What is the maximum number of field devices supported per H1 network segment?

Each H1 network segment supports up to 16 FOUNDATION Fieldbus devices.

Where can the device be installed within an Experion system?

The double slot-width chassis module installs in an Experion C200 Controller rack or in a remote I/O chassis rack.

What cable types are used to connect the unit to Remote Termination Panels?

The module connects to Remote Termination Panels (RTPs) using TC-FFCxxx series Fieldbus RTP cables.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Greyish White
Country of origin
United States

Recently Viewed Products

Technical knowledge

Modernizing Bailey INFI 90 Symphony HMIs Running on OpenVMS Alpha

A practical guide to replacing aging Bailey Symphony operator stations running on OpenVMS Alpha. It compares Alpha emulation, OpenVMS x86 migration, OPC re-platforming, and phased ABB modernization.

Why Maintenance Data Is Essential for Industrial Reliability

Maintenance data connects work orders, sensor signals, asset history, costs, and technician knowledge. Used well, it improves planning, reliability, predictive maintenance, spare-parts control, and...

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...