Omron

Omron G9SX-EX401-RT G9SX Series Flexible Safety Expansion Unit

SKU G9SX-EX401-RT

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Omron

  • Product No.: G9SX-EX401-RT

  • Country of origin:Japan

  • Product Type: Safety Relay Expansion Modules

  • Payment: T/T, Western Union

  • Weight: 1500g

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

Integrating directly into master safety architectures, the Omron G9SX-EX401-RT expansion module expands the output capabilities of standard safety systems by providing additional instantaneous relay channels. Operating on a 24 VDC supply, this unit features 4 instantaneous safety outputs and 1 auxiliary feedback output, allowing industrial automation systems to scale safety-related control circuits without compromising response speed or diagnostic visibility. Designed with robust screw terminals, it ensures high vibration resistance and secure wiring connections in demanding industrial environments.

Key Features

  • Instantaneous Safety Expansion: Adds 4 highly reliable, instantaneous electromechanical safety outputs to a master controller.
  • Secure Inter-Unit Linking: Connects directly to G9SX-series master modules via safe logical connections.
  • Auxiliary Diagnostic Output: Features 1 auxiliary output for standard PLC monitoring and fault reporting.
  • Industrial-Grade Screw Terminals: RT-designated model incorporates heavy-duty screw terminals for robust field wiring.

Applications

  • Expansion of safety output circuits for light curtains, E-stop loops, and safety door switches.
  • Multi-zone safety system integration in high-capacity manufacturing lines.
  • Automated packaging systems requiring independent or grouped emergency stop zones.

Technical Specifications

Parameter Specification Value
Manufacturer Omron
Model Code G9SX-EX401-RT
Series G9SX Series
Device Type Flexible Safety Expansion Unit
Rated Supply Voltage 24 VDC
Operating Voltage Range -15% to 10% of rated supply voltage
Rated Power Consumption 2 W maximum
Safety Relay Outputs 4 instantaneous outputs (DPST-NO x 2)
Auxiliary Outputs 1 auxiliary semiconductor output
Rated Load 250 VAC, 3 A / 30 VDC, 3 A (resistive load)
Rated Carry Current 3 A
Operating Time (OFF to ON) 30 ms maximum
Response Time (ON to OFF) 10 ms maximum
Mechanical Durability 5,000,000 cycles minimum (switching frequency: 7,200 cycles/hour)
Electrical Durability 100,000 cycles minimum (rated load, switching frequency: 1,800 cycles/hour)
Terminal Type Screw terminals
Product Net Weight 0.165 kg
Shipping Weight (Calculated) 1.50 kg

Empirical Engineering Insights

Alternative Models & Compatibility

This expansion unit must always be matched with a master G9SX unit (e.g., G9SX-AD or G9SX-ADA series). It cannot operate as a standalone safety relay. When replacing older Omron safety expansion modules, verify terminal footprints; the RT model features screw terminals, which differ from spring-cage (RC) variants.

Application Pitfalls & Engineering Notes

When calculating the safety integrity level (SIL) and performance level (PL) for your safety loop, remember to add the 10 ms maximum response time of the expansion unit to the response time of your master G9SX unit. Ignoring this cumulative propagation delay can lead to insufficient safety distances for light curtains and emergency stop stations.

Commissioning & Wiring Tips

Ensure that the cross-unit connection cable is fully locked into place on both sides before applying 24 VDC control power. Powering the system up with a loose or partially inserted communication bus connector will cause the master module to enter a critical system fault mode, requiring a full power cycle to reset.

Installation Guidelines

CRITICAL WARNING: De-energize all primary and auxiliary power sources before handling, mounting, or wiring this device. Failure to completely isolate power can result in electrical shock, unexpected machine startup, or irreversible damage to the internal safety relays.
1
Mount the expansion unit securely onto a standard 35 mm DIN rail immediately adjacent to the master G9SX safety unit.
2
Connect the lateral expansion bus connector from the master controller to the side socket of the expansion unit until it clicks firmly into place.
3
Wire the 24 VDC power supply terminals and individual safety outputs, ensuring that all screw terminals are torqued according to OEM specifications.

FAQ

Can the G9SX-EX401-RT function as a standalone safety relay?

No. The G9SX-EX401-RT is an expansion module and requires a compatible G9SX master safety controller to provide safety logic processing and power.

What is the differences between the RT and RC models in this series?

The RT version is equipped with standard screw terminal blocks, whereas the RC version features spring-cage tension terminals for toolless wiring.

How does this expansion unit affect the system safety response time?

The G9SX-EX401-RT adds a maximum response time of 10 ms (ON to OFF) which must be added to the response time of the master safety unit for system-wide safety distance calculations.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 5 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Japan

Technical knowledge

1756-OF4 Output Wrong? Check Mode, RTB, and Scaling First

A field-first diagnostic sequence for 1756-OF4 analog output problems: channel mode, removable terminal block, scaling, and controlled electrical checks.

1746-OA8 vs 1746-OA16: Output Count and Current Limits

A direct comparison of 1746-OA8 and 1746-OA16 output count, common grouping, backplane current and temperature-derated load limits.

Replacing a 1761-NET-DNI: Capture These Settings First

A field checklist for recording the 1761-NET-DNI hardware series, firmware, EDS file, DF1 settings, DeviceNet address and messaging configuration before replacement.

EL3062 vs EL3062-0030: The Input Range Changes

The EL3062 is a 0–10 V EtherCAT terminal. The EL3062-0030 is a 0–30 V variant. This checklist covers identification, scaling and commissioning.

Replacing a 1769-OW8: Checks Before Moving Relay Loads

A field checklist for replacing Allen-Bradley 1769-OW8 relay output modules without losing load-group, wiring, and commissioning details.

PLC I/O Modules: Wiring, Load, and Isolation Checks

A field checklist for matching PLC digital and analog I/O to sensors, loads, commons, isolation groups, filters, and replacement settings.