Description

The 7ML5221-1BC11 is a SITRANS Probe LU ultrasonic level transmitter engineered for continuous, non-contact level and volume monitoring of liquids and slurries. This device offers a measurement range of up to 6 meters (20 ft) and utilizes an advanced echo processing algorithm to ensure reliable performance in diverse industrial environments. Equipped with a 4-20 mA HART communication output, it allows for easy integration into existing control systems and remote monitoring architectures. The transmitter features a durable PVDF copolymer transducer and a G 2" (BSPP) process connection, making it suitable for a wide range of vessel types and process conditions.

Features

  • Technology: Ultrasonic non-contact measurement for level and volume.
  • Measurement Range: Up to 6 meters (20 ft).
  • Output: 4-20 mA with HART communication.
  • Transducer Material: PVDF copolymer (chemical resistant).
  • Process Connection: G 2" (BSPP), EN ISO 228-1.
  • Enclosure: Plastic (PBT) with 2 x M20 cable inlets.
  • Certifications: General purpose, FM, CSA, CE, C-TICK, KCC.

Applications

  • Liquid level monitoring in storage tanks and process vessels.
  • Slurry level measurement in industrial waste or mining applications.
  • Volume calculation for chemical storage.
  • Wastewater and utility monitoring.

Technical Specifications

Feature Specification
Manufacturer Siemens
Range SITRANS
Model 7ML5221-1BC11
Measurement Range 6 meters (20 ft)
Process Connection G 2" (BSPP)
Transducer Material PVDF Copolymer
Communication 4-20 mA, HART
Enclosure Material Plastic (PBT)
Weight 2.20 kg
Origin Siemens

Installation Guidelines

  • Mounting: Install the transmitter in a vertical position, ensuring the transducer face is clear of any obstructions such as agitators, fill pipes, or tank walls that could cause false echoes.
  • Environment: Avoid mounting the unit in areas with heavy turbulence or excessive foaming on the liquid surface, as these conditions can impede ultrasonic wave propagation.
  • Wiring: Use shielded, twisted-pair cabling for the 4-20 mA HART loop to prevent electromagnetic interference. Ensure all cable glands are tightened securely to maintain the integrity of the enclosure.
  • Configuration: Utilize the HART protocol to configure parameters such as tank dimensions, material type, and damping constants during the initial commissioning phase.
  • Maintenance: Periodically inspect the transducer face for buildup; clean using non-abrasive materials to ensure signal accuracy.

FAQ

What is the maximum measuring range of the 7ML5221-1BC11?

This specific model has a measurement range of 6 meters (20 ft).

What communication protocols does this transmitter support?

The device supports 4-20 mA current loop output with HART communication.

What material is the transducer made of?

The transducer is constructed from PVDF copolymer, which provides excellent resistance to a variety of process chemicals.

Can this device monitor both level and volume?

Yes, the SITRANS Probe LU is designed to monitor both the level and the calculated volume of liquids and slurries in industrial tanks.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 5 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
White
Country of origin
Germany

Technical knowledge

IC693CPU360 vs IC693CPU364: Ethernet and Power Budget

Compare the IC693CPU360 and IC693CPU364 by Ethernet interface, +5 VDC load, memory, rack limits, and replacement checks.

1756-OF4 Output Wrong? Check Mode, RTB, and Scaling First

A field-first diagnostic sequence for 1756-OF4 analog output problems: channel mode, removable terminal block, scaling, and controlled electrical checks.

1746-OA8 vs 1746-OA16: Output Count and Current Limits

A direct comparison of 1746-OA8 and 1746-OA16 output count, common grouping, backplane current and temperature-derated load limits.

Replacing a 1761-NET-DNI: Capture These Settings First

A field checklist for recording the 1761-NET-DNI hardware series, firmware, EDS file, DF1 settings, DeviceNet address and messaging configuration before replacement.

EL3062 vs EL3062-0030: The Input Range Changes

The EL3062 is a 0–10 V EtherCAT terminal. The EL3062-0030 is a 0–30 V variant. This checklist covers identification, scaling and commissioning.

Replacing a 1769-OW8: Checks Before Moving Relay Loads

A field checklist for replacing Allen-Bradley 1769-OW8 relay output modules without losing load-group, wiring, and commissioning details.