Yokogawa

Yokogawa AAI135-S03 CENTUM VP Analog Input Module

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Yokogawa

  • Country of origin:Japan

  • Product Type: Analog Input Module

  • Payment: T/T, Western Union

  • Weight: 300g

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The Yokogawa AAI135-S03 (Replaced by AAI135-S53) is a high-performance analog input module belonging to the CENTUM VP distributed control system (DCS) series. Purpose-built to receive standard 4 to 20 mA industrial field signals, this module features an 8-channel input configuration with complete galvanic channel-to-channel isolation. The specific suffix layout designates this hardware as a standard type engineered with no explosion protection options. To ensure uninterrupted loop tracking in aggressive plant environments, the unit comes outfitted with an ISA Standard G3 chemical corrosion-resistant conformal coating option and an extended temperature endurance qualification spanning from -20 to 70 degC. Each field pathway is thoroughly isolated from both the system backplane and neighboring channels, allowing for seamless integration into high-availability, dual-redundant control system topologies.

Features

  • Deployed within the CENTUM VP control platform supporting dual-redundant hot-standby architectures.
  • Features 8 analog input channels with complete galvanic field-to-system and channel-to-channel electrical isolation.
  • Integrated transmitter power supply capability designed directly into the input circuit loops to drive 2-wire instruments.
  • Enhanced hardware durability via ISA Standard G3 conformal coating for harsh chemical or corrosive environments.
  • Extended thermal operational profile rated for steady execution from -20 up to 70 degC.
  • Supports advanced field asset diagnostics via native digital HART communication.

Applications

  • High-density process monitoring loops in refinery, petrochemical, and power generation facilities.
  • High-integrity instrumentation setups requiring dedicated channel isolation to eliminate ground loops.
  • Distributed control infrastructure positioned in aggressive, unconditioned outdoor environment spaces.
  • Safety-critical or high-availability processing lines demanding dual-redundant input configurations.

Ordering Information

Model/Suffix Code Option Specification
AAI135 Analog Input Module (4 to 20 mA, 8-channel, Isolated channels)
-S Standard type
0 (5) With no explosion protection
3 With ISA Standard G3 option and temperature (-20 to 70 degC) option

Technical Specifications

Items Specifications
Manufacturer Yokogawa
Model AAI135-S03 (Replaced by AAI135-S53)
Number of I/O channels 8-channel input, isolated channels
I/O signal 4 to 20 mA
Allowable input current 25 mA
Withstanding voltage

Between input and system: 500 V AC, for 1 minute


 

Between input channels: 500 V AC, for 1 minute

Input resistance

Power ON: 290 Ohm (at 20 mA) to 450 Ohm (at 4 mA)


 

Power OFF: 500 kOhm or larger

Allowable load resistance —
Circuit-open detection —
Accuracy ±16 uA
Data update period 10 ms
Transmitter power supply 15.0 V or higher (at 20 mA); 29.3 V or less (at 0 mA)
Temperature drift ±16 uA / 10 degC
Maximum current consumption 360 mA (5 V DC), 450 mA (24 V DC)
Weight 0.3 kg
External connection Pressure clamp terminal, MIL connector cable, dedicated cable
HART communication Available

Installation Guidelines

  • Align and insert the input module into its specified node backplane interface slot within the CENTUM VP rack, confirming that all backplane connectors latch with zero binding tension.
  • Maintain critical loop protection constraints: A Zener barrier is not allowed to be connected with this module. An isolation barrier must be implemented when deploying this device within intrinsically safe field loops.
  • For installations routing through a MIL connector cable interface, check that the overall application withstanding voltage limitations conform to the distinct technical boundaries of the chosen wiring cable harness.
  • Keep cabinet ventilation channels clear to permit optimal convection airflow, ensuring internal temperatures stay safely inside the designated -20 to 70 degC envelope.

FAQ

Does the module support the connection of external Zener barriers?

No, a Zener barrier is not allowed to be connected with this module. An isolation barrier must be used instead when the device is deployed in intrinsically safe applications.

What are the exact channel isolation capabilities of this device?

The module features complete isolation between the field circuits and the internal system logic, as well as galvanically isolated pathways between each individual input and output channel, rated at 500 V AC for 1 minute.

How does the allowable load resistance change under high operating temperatures?

The standard allowable load resistance for the output channels is 0 to 750 Ohm. However, when the module is used in ambient temperatures from 60 to 70 degC inside a conforming ER bus node unit, the allowable load resistance adjusts to a window of 200 to 750 Ohm.

What happens to the module input resistance when the system is powered down?

When the power is ON, the input resistance varies dynamically from 290 Ohm (at 20 mA) to 450 Ohm (at 4 mA). When the power is OFF, the input resistance switches to a high impedance state of 500 kOhm or larger.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Yokogawa AAI135-S03 CENTUM VP Analog Input Module

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 20 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Japan

Technical knowledge

Replacing Yokogawa AAI835: Wiring and Barrier Checks Before Swap

Before replacing a Yokogawa AAI835, verify the 4-in/4-out channel map, power-loss loop behavior, barrier type, output load, cable, and redundancy.

ABB PM891K01 Replacement: Check Redundancy Before Ordering

ABB PM891K01 article 3BSE053241R1 is the non-redundant AC 800M processor kit. Use this field checklist before replacement.

ABB TP853 Replacement Checks for CI853/CI855/CI857/CI861

Replacement checks for ABB TP853 3BSE018126R1: identify the installed CI853, CI855, CI857, or CI861 interface, record wiring, and verify communication after installation.

5069-L330ERMS2 Startup Checks: RTBs, I/O, and Motion Limits

Engineering checks for the Allen-Bradley 5069-L330ERMS2: controller capacity, separate RTB kits, local I/O limits, network-node limits, and motion-axis count.

Replacing ABB DSQC 351: Controller and Network Checks

Checks to record before replacing ABB 3HNE 00006-1 DSQC 351: controller generation, X3/X5/X20/X21 wiring, DeviceNet settings, INTERBUS mapping, and LED states.

IC693CPU360 vs IC693CPU364: Ethernet and Power Budget

Compare the IC693CPU360 and IC693CPU364 by Ethernet interface, +5 VDC load, memory, rack limits, and replacement checks.