Description

To analyze three-phase AC power networks directly within the industrial fieldbus segment, the Beckhoff EL3403 provides precise, high-performance measurement values. This 3-channel analog input power measurement terminal is designed to calculate comprehensive electrical grid status parameters, including effective power, reactive power, apparent power, energy consumption, phase angle (cos phi), and frequency for each connected phase. Processing inputs up to 500 V AC directly, the module supports highly detailed diagnostics of energy distribution systems and industrial machinery. Non-intrusive current sensing up to 1 A (AC) is executed through external measuring transformers (such as x A/1 A), enabling flexible integration into existing power distribution frameworks.

Features

  • Mains-synchronous conversion with 16-bit resolution for premium signal acquisition.
  • Direct RMS value calculation for all applied voltage and current waveforms.
  • Comprehensive data calculation: delivers current, voltage, active/reactive/apparent power, energy, frequency, and phase angle values directly over the E-bus.
  • Optional single-phase operation mode for simplified monitoring on isolated lines.
  • Galvanic electrical isolation rating of 1500 V to isolate low-voltage logic from high-voltage measuring points.
  • Compact 12 mm design form factor optimizing space layout on industrial DIN rails.

Applications

  • Real-time energy management and sub-metering in industrial production facilities.
  • Dynamic load monitoring and diagnostic tracking on high-power three-phase AC motors.
  • Integration within power distribution plants and substation cabinets for utility tracking.
  • Predictive maintenance analytics based on power signature variations.

Technical Specifications

Manufacturer BECKHOFF
Part Number / Model EL3403
Technology 3-phase power measurement for alternating voltages
Number of Inputs 3 x current, 3 x voltage
Measuring Voltage Max. 500 V AC 3~ (ULX-N: max. 288 V AC)
Measuring Current Max. 1 A AC (via measuring transformers x A/1 A)
Resolution 1 uA, 0.1 mV, 10 mW (16-bit)
Measuring Error 0.5% relative to full scale value (U/I), 1% calculated values
Measuring Procedure True RMS calculation
Conversion Time Mains-synchronous
Electrical Isolation 1500 V
Current Consumption E-bus Typ. 120 mA
Process Image Bit Width 62 byte PM input, 3 byte PM output
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Relative Humidity 95%, non-condensing
Enclosure Protection Rating IP20
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Weight Approx. 75 g

Connections and Interfaces

Connection Property Specification
Wiring Method Solid conductor (e), flexible conductor (f), and ferrule (a)
Actuation Method Spring actuation by screwdriver
Connection Cross-Section (Solid/Stranded) 0.08 to 2.5 mm² (AWG 28 to 14)
Connection Cross-Section (With Ferrule) 0.14 to 1.5 mm² (AWG 26 to 16)
Stripping Length 8 to 9 mm
Current Load Power Contacts Max. 10 A

Installation Guidelines

  • Mount the terminal onto a standard 35 mm DIN rail conforming to EN 60715, locking it firmly into place.
  • Ensure double slot and key mechanical connection is completely flush with adjacent terminals.
  • Route high-voltage measurement lines separated from low-voltage E-bus and signal lines to prevent noise coupling.
  • Install appropriate external current transformer shorting blocks for safety during troubleshooting or hardware swap-outs.

Compliance and Certifications

  • CE
  • UL listed
  • EMC Immunity/Emission: Conforms to EN 61000-6-2 / EN 61000-6-4
  • Vibration/Shock Resistance: Conforms to EN 60068-2-6 / EN 60068-2-27
Loading product navigation…

What parameters can the Beckhoff EL3403 calculate and display?

The EL3403 measures voltage, current, effective power, reactive power, apparent power, energy consumption, phase angle (cos phi), and frequency for each of the three channels.

Does the EL3403 support single-phase operation?

Yes, while the terminal is optimized for 3-phase power measurement on AC networks, it also supports optional single-phase configuration.

What is the maximum voltage input direct rating of the EL3403?

The terminal is rated for a maximum measuring voltage of 500 V AC 3-phase (with ULX-N rating at a maximum of 288 V AC).

How is the current measured using this EtherCAT terminal?

The module measures AC current up to 1 A, which is typically routed via external, standard measuring transformers configured as x A / 1 A.

What is the mechanical environmental protection rating of the EL3403?

The terminal has an IP20 protection rating and is designed for cabinet installation on a 35 mm DIN rail.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendemos mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Aceitamos devoluções de produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso site oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Alemanha

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Sistemas Hidráulicos: Um Guia Prático de Automação Industrial

Este artigo explica como os atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação, dentro da automação industrial. Ele mostra...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas em FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem às...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel fundamental na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das mandíbulas mecânicas tradicionais. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...