1 de 1

Mitsubishi Electric GT1275-VNBA GOT1000 Touch Screen HMI

Mitsubishi Electric GT1275-VNBA GOT1000 Touch Screen HMI

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: Mitsubishi Electric

  • Nº do Produto: GT1275-VNBA

  • País de origem:Estados Unidos

  • Tipo de Produto: Touch Screen HMIs

  • Pagamento: T/T, Western Union

  • Peso: 2300g

  • Dimensões: 340 mm x 280 mm x 125 mm

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver detalhes completos

Description

Facilitating high-resolution plant-floor visualization, the Mitsubishi Electric GT1275-VNBA functions as an industrial operator interface within the GOT1000 platform. This 10.4-inch TFT liquid crystal display provides sharp graphical monitoring and robust control capabilities over diverse automated systems. Operating on a universal 100 to 240VAC power supply, the unit integrates essential fieldbus and Ethernet communication options directly onto its main board, making it a reliable choice for monitoring complex industrial machinery and distributed assembly operations.

Features

  • High-Contrast Display: 10.4-inch TFT color LCD screen displaying 256 colors with a clear 640 x 480 pixel VGA resolution.
  • Versatile Power Compatibility: Accepts wide-range AC input from 100 to 240VAC (50/60Hz) to simplify integration across global regional grids.
  • Multi-Port Connectivity: Built-in Ethernet, RS-422/485, and RS-232 interfaces accommodate simultaneous multi-channel controller communication.
  • Data Management: Integrated SD memory card slot and USB port permit rapid project transfer, logging, and OS backups.
  • Industrial Durability: Front-panel rating matching IP67F environmental standards provides protection against dust, water ingress, and oil spray.

Applications

  • Automotive assembly and robotic workcell control panels.
  • Water and wastewater treatment plant visualization interfaces.
  • Packaging, food processing, and material handling machinery.
  • Distributed PLC network monitoring in central control rooms.

Technical Specifications

Parameter Specification Value
Manufacturer Mitsubishi Electric
Model Number GT1275-VNBA
Series GOT1000 (GT12 Series)
Display Technology TFT Color LCD
Screen Size 10.4 inches (diagonal)
Resolution 640 x 480 pixels (VGA)
Display Colors 256 colors
Input Power Supply 100 to 240VAC (+10%, -15%)
Frequency Rating 50 / 60 Hz (+/-5%)
Power Consumption 41VA or less (at maximum load)
Inrush Current 40A or less (for 4 ms at max load)
Touch Panel Type Analog resistive
Operating Temperature 0 to 50 degC
Protection Rating IP67F (front face when panel-mounted)
Net Hardware Weight 2.3 kg (5.07 lbs)
Shipping Weight (Calculated) 3.5 kg
Package Dimensions (Calculated) 340 mm x 280 mm x 125 mm

Connections and Interfaces

Interface / Connector Function / Circuit Assignment
Ethernet (RJ45) 10BASE-T/100BASE-TX interface for high-speed PLC data link and diagnostic network configurations
RS-422/485 (D-Sub 9-Pin Female) Direct connection to FX series, Q series, or third-party serial controllers and microcontrollers
RS-232 (D-Sub 9-Pin Male) Connection port for bar code readers, personal computers, or specialized serial hardware
USB Mini-B (Device) Dedicated PC transfer interface for application screen creation and testing via GT Works3
USB Type A (Host) External storage connection for memory drives to record trends, transfer boot parameters, or load projects
SD Card Slot Expansion storage accepting SD/SDHC media card for immediate local program backups and historical logging

Alternative Models & Compatibility

The GT1275-VNBA serves as an excellent upgrade path for older GT1175 series devices. While sharing similar panel cutout dimensions, the GT1275 integrates built-in Ethernet, removing the need for auxiliary serial-to-Ethernet converters. Upgrading projects from legacy software tools is fully supported inside GT Designer3, ensuring low-risk software migration.

Application Pitfalls & Engineering Notes

To prevent thermal throttling and maintain display longevity, avoid installing the HMI in direct sunlight or within high-temperature enclosures exceeding 50 degC. When mounting inside completely closed panels, provide at least 100 mm of clear space above and below the rear ventilation slots to allow natural convective heat dissipation.

Commissioning & Wiring Tips

Always ensure that the functional ground (FG) terminal on the AC power block is connected using a dedicated ground lead (minimum 2 mm squared wire) directly to a unified machine ground. This reduces local electromagnetic interference (EMI) from neighboring variable frequency drives (VFDs) which can otherwise interfere with the HMI analog touch panel sensitivity.

Installation Guidelines

CRITICAL WARNING

Isolate and lock out all upstream electrical power supplies before performing installation, mounting, or terminal wiring. Verify that no residual voltage remains using an electrical tester to prevent severe electrical shock or damage to the unit's internal circuitry.

1

Prepare Panel Cutout

Create a panel cutout matching the standard dimensions of 289 mm x 200 mm, ensuring the panel thickness is between 2.0 mm and 4.0 mm.

2

Check Panel Gasket

Verify that the rubber water-resistant gasket is securely seated in its channel around the back bezel of the HMI unit prior to insertion.

3

Insert and Secure Mounts

Insert the HMI into the cutout from the front of the panel. Fasten the provided mounting brackets to the rear casing, tightening the screws to a precise torque of 0.36 to 0.48 N.m to ensure a dust-tight, waterproof seal.

4

Connect Power Terminals

Route 100-240VAC power lines through a class-D grounded distribution point. Connect securely to the terminals on the back, and ground the functional ground terminal immediately.

Loading product navigation…

Can I download projects to the GT1275-VNBA using Ethernet?

Yes. The HMI features an integrated RJ45 10BASE-T/100BASE-TX port. You can download and upload application projects directly through GT Works3 after configuring the communication settings to match your network subnet.

Does this model support logging data directly to local storage?

Yes, historical alarm data, event logs, and system trends can be configured within the design software to save locally onto an SD memory card or a standard USB flash drive formatted in FAT/FAT32.

What software is used to program the GT1275-VNBA HMI?

This unit is fully programmed and configured using Mitsubishi Electric's standard screen design package, GT Works3 (specifically GT Designer3).

How do I maintain the IP67F front-panel rating during installation?

You must ensure the physical mounting panel surface is flat and unwarped, the rubber gasket is completely seated, and the mounting brackets are tightened uniformly to the recommended torque of 0.36 to 0.48 N.m.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reabastecimento e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Estados Unidos

Produtos Visualizados Recentemente

Conhecimento técnico

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crítico na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Desde o Manuseio Delicado até a Automação Pesada

As garras robóticas modernas estão evoluindo além das mandíbulas mecânicas tradicionais. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...

Retrospectiva: Como os Primeiros Motores Elétricos Mudaram a Mineração Subterrânea

De compressores CC acionados por corda a carrinhos de mina movidos a bateria, as operações de mineração iniciais marcaram um ponto de virada na eletrificação industrial. Este artigo explora como os...

Factory I/O: Uma Ferramenta Moderna de Simulação de CLP para Treinamento em Automação Industrial

Factory I/O está transformando a educação em CLP ao oferecer simulações industriais 3D imersivas para estudantes, engenheiros e equipes de manutenção. A plataforma reduz a distância entre a teoria e...