1 از 1

Beckhoff EPP1518-0002 EtherCAT P Box

Beckhoff EPP1518-0002 EtherCAT P Box

فقط 10 قلم کالا در انبار باقی مانده است
  • تولیدکننده: BECKHOFF

  • شماره محصول: EPP1518-0002

  • کشور سازنده:آلمان

  • نوع محصول: EtherCAT P I/O Modules

  • پرداخت: حواله بانکی (T/T)، وسترن یونیون

  • وزن: 500g

  • بندر حمل و نقل: شیامن

  • گارانتی: ۱۲ ماه

تعداد
مشاهده جزئیات کامل

Description

Facilitating direct sensor integration within decentralized control architectures, the BECKHOFF EPP1518-0002 industrial interface module provides eight digital inputs inside an IP67-rated enclosure. This EtherCAT P Box integrates communication and power (Us and Up) into a single, compact P-coded M8 connector system, minimizing on-site cabling complexity. Constructed with rugged encapsulation technology, the device is designed for direct machine mounting without an electrical cabinet, ensuring fast data transmission and high-precision time synchronization via integrated Distributed Clocks (DC).

Features

  • 8 Digital Inputs: Supports direct connection of 24 V DC sensors with flexible filter configuration options.
  • High-Speed Counting: Includes 2 inputs that can be configured as 32-bit up/down counters operating at frequencies up to 1 kHz.
  • Single-Cable Automation: Uses M8 P-coded EtherCAT P technology to combine system/sensor power, peripheral voltage, and EtherCAT telemetry.
  • Industrial-Grade Protection: Sealed housing rated at IP65, IP66, and IP67 for reliable operation in wet, dusty, and high-vibration environments.
  • TwinCAT Integration: Fully compatible with TwinCAT engineering systems for diagnostics, state-monitoring, and parameter configuration.

Applications

  • Decentralized Assembly Lines: Standardized on-machine mounting close to pneumatic valves and proximity sensors.
  • Material Handling & Conveyors: Reliable high-speed input capture for sorting and tracking sensors under high vibration.
  • Automotive Test Benches: Multi-sensor signal acquisition with microsecond-level synchronization using Distributed Clocks.

Technical Specifications Table

Parameter Specification Value
Manufacturer Beckhoff
Model Number EPP1518-0002
Product Protocol EtherCAT P
Number of Inputs 8 (2 configurable as 32-bit up/down counters)
Bus Interface Connection 2 x M8 socket, shielded, screw-type, P-coded
Input Port Type M12 x 1, 5-pin, A-coded
Nominal Input Voltage 24 V DC (-15% / +20%)
Logic "0" Signal Voltage -3 to +5 V DC (EN 61131-2, type 3)
Logic "1" Signal Voltage 11 to 30 V DC (EN 61131-2, type 3)
Input Current Rating Typ. 3 mA (EN 61131-2, type 3)
Input Filter Config Range Adjustable, 0 to 100 ms
Sensor Power Supply From Us control voltage, max. 0.5 A per 4 sensors (short-circuit proof)
Current Consumption (Us) Typ. 100 mA
Electrical Isolation 500 V RMS
Operating Temperature Range -25 to +60 degC
Storage Temperature Range -40 to +85 degC
Protection Rating IP65, IP66, IP67 (conforms to EN 60529)
Weight Approx. 165 g
Shipping Weight (Calculated) 0.45 kg

Connections and Interfaces

Connector Port Terminal Pin Signal Assignment
M8 P-coded (Power & EtherCAT) Pin 1 Us (System and Sensor Power +24 V DC)
Pin 2 Up (Actuator / Peripheral Power +24 V DC)
Pin 3 GNDs (System/Sensor Ground)
Pin 4 GNDp (Actuator/Peripheral Ground)
M12 A-coded (Digital Input Ports) Pin 1 Sensor Supply +24 V DC (Us)
Pin 2 Input Signal B (Channels 2, 4, 6, 8)
Pin 3 GNDs (Sensor Ground)
Pin 4 Input Signal A (Channels 1, 3, 5, 7)
Pin 5 Functional Earth (FE) / Shield

Empirical Engineering Insights

Alternative Models & Compatibility

The EPP1518-0002 belongs specifically to the EtherCAT P family. It is physically incompatible with standard EtherCAT EP-series boxes that use standard M8 Ethernet keying. If you are converting a system from standard EtherCAT to EtherCAT P, you must use an integration splitter such as the EP9224-0037 to transition power and standard network nodes safely onto the P-coded network infrastructure.

Application Pitfalls & Engineering Notes

When daisy-chaining multiple EPP modules, calculate cumulative current drop across both Us (system) and Up (peripheral) buses. While each local sensor supply channel is short-circuit proof up to 0.5 A, overloading the primary M8 feed lines will cause internal bus drops, triggering undervoltage fault states logged in the TwinCAT Master. Use the TwinCAT System Manager software to calculate voltage curves before site commissioning.

Commissioning & Wiring Tips

Ensure that all unused M12 and M8 connections are sealed using correct protective IP67 plastic caps. Leaving ports open in wet or humid processing environments compromises the sealing of the entire module block and can result in intermittent short-circuits between the sensor supply and ground pins.

Installation Guidelines

CRITICAL WARNING: Verify that all upstream and field power supplies are fully de-energized prior to connecting or disconnecting any M8 or M12 cables. Hot-plugging P-coded power lines can cause electrical arc damage to contact pins, degrading communication and risking module failure.
1

Mount the device directly to your machine frame or profiles using two M3 screws. Ensure the mounting surface is clean and level to avoid twisting stresses on the IP67 housing.

2

Connect the incoming EtherCAT P cable to the upper P-coded M8 socket, locking the coupling ring securely to maintain seal integrity.

3

Wire digital sensors to the M12 input sockets. Program appropriate digital input filter parameters within TwinCAT (0 to 100 ms) depending on sensor type to prevent mechanical contact bounce issues.

Loading product navigation…

Can I connect standard EtherCAT devices directly to the EPP1518-0002?

No. The module uses M8 P-coded EtherCAT P connectors, which combine power and Tx/Rx data. Standard EtherCAT uses different pinouts and keying. You must use an EtherCAT P junction or splitter module like the EP9224 to transition from standard EtherCAT to EtherCAT P.

What is the maximum limit for the integrated 32-bit up/down counters?

The two configurable counter inputs support a maximum counting frequency of 1 kHz. They can be read and evaluated directly within the TwinCAT environment as 32-bit values.

How does the module handle short circuits on the sensor supply?

The sensor supply is derived from the Us control voltage and is short-circuit proof. It allows a maximum current draw of 0.5 A per group of 4 sensors, preventing a local wiring fault from disabling the entire module.

ارسال سریع جهانی

  • تحویل استاندارد: ۴-۶ روز کاری از طریق DHL، FedEx و UPS.
  • ارسال فوری: ارسال همان روز برای سفارش‌های موجود در انبار که قبل از ساعت ۲:۰۰ بعدازظهر (GMT+8) ثبت شده‌اند.
  • پوشش جهانی: خدمات به بیش از ۱۵۰ کشور، شامل تحویل سریع به عربستان سعودی و امارات.

بازگشت کالا و گارانتی

  • ضمانت ۳۰ روزه: بازگشت کالا برای محصولات موجود در انبار با بسته‌بندی اصلی و مهر کارخانه پذیرفته می‌شود.
  • گارانتی ۱۲ ماهه: هر قطعه صنعتی با گارانتی فنی حرفه‌ای ما پشتیبانی می‌شود.

سفارش‌ها از دوشنبه تا جمعه پردازش و تحویل داده می‌شوند (به جز تعطیلات رسمی).


برای شرایط کامل واجد شرایط بودن، هزینه‌های بازگردانی و جزئیات بازگشت بین‌المللی، لطفاً سیاست رسمی ما را مشاهده کنید سیاست بازپرداخت و بازگشت کالا .

TECHNICAL SPECIFICATIONS

Country of origin
آلمان

محصولات مشاهده‌شده اخیر

دانش فنی

عملگرهای الکتریکی طراحی شده برای جایگزینی سیستم‌های نیروی سیال: راهنمای عملی اتوماسیون صنعتی

این مقاله توضیح می‌دهد که چگونه عملگرهای الکتریکی یکپارچه، مانند سری e-Actuator شرکت SMC، در حال تحول کنترل حرکت صنعتی با جایگزینی سیستم‌های سنتی پنوماتیک و هیدرولیک هستند. این مقاله به بهبود دقت...

عملیات ریاضی با استفاده از OpenPLC برای کاربردهای اتوماسیون صنعتی

این مقاله توضیح می‌دهد که چگونه سیستم‌های PLC عملیات ریاضی اصلی مانند جمع، تفریق، ضرب، تقسیم، مدول و توان را در اتوماسیون صنعتی انجام می‌دهند. نشان می‌دهد که چگونه این بلوک‌های عملکردی سیگنال‌های خام...

منطق بولی پیشرفته با برنامه‌نویسی FBD PLC: کاربردهای عملی صنعتی فراتر از منطق پایه

این مقاله چندین تابع پیشرفته منطق بولی را که در برنامه‌نویسی PLC فراتر از عملیات پایه AND، OR و NOT استفاده می‌شوند، توضیح می‌دهد. همچنین نحوه استفاده از ابزارهایی مانند جداول صحت، مالتی‌پلکسرها،...

منطق بولی در برنامه‌نویسی PLC: درک گیت‌های منطقی FBD

منطق بولی پایه و اساس هر برنامه PLC است. از کنترل‌های ساده ماشین تا سیستم‌های پیچیده اتوماسیون صنعتی، دروازه‌های منطقی تعیین می‌کنند که کنترل‌کننده‌ها چگونه به ورودی‌ها و شرایط عملیاتی متغیر پاسخ...

راهنمای جامع فایروال‌های صنعتی و تقسیم‌بندی شبکه OT

فایروال‌های صنعتی نقش حیاتی در امنیت سایبری OT ایفا می‌کنند و با استفاده از تقسیم‌بندی، کنترل ورودی/خروجی و ادغام IDS/IPS مطابق با اصول IEC 62443، از شبکه‌های PLC، DCS و SCADA محافظت می‌کنند.

راهنمای گیره‌های رباتیک: از جابجایی ظریف تا اتوماسیون سنگین

گیره‌های رباتیک مدرن فراتر از فک‌های مکانیکی سنتی در حال پیشرفت هستند. از سیستم‌های چسبنده الهام‌گرفته از گکوی، گیره‌های نرم با درجه‌بندی غذایی تا ابزارهای انبار مجهز به هوش مصنوعی، فناوری‌های...