The Emerson KJ3002X1-BG2 is a Thermocouple, mV Card developed for the DeltaV scalable process system. This interface component enables the direct conversion of low-level analog millivolt signals from temperature sensors and standard voltage sources into structured digital data for process automation loops. Operating on local bus infrastructures, the KJ3002X1-BG2 interfaces field temperature variables with central system controllers across diverse hazardous industrial plant architectures.

Features

  • Integrates a dedicated rotary keying mechanical mechanism to guarantee hardware alignment between interface units and field terminal blocks.
  • Features integrated diagnostic capability and electrical isolation design tailored for low-amplitude sensor signal routing.
  • Contains internal electrical path tracing optimized for direct field thermocouple and millivolt sensor hookups without external conversion hardware.

Applications

  • High-temperature process furnaces and process vessel monitoring.
  • Thermal monitoring infrastructures in industrial processing environments.
  • Continuous temperature multi-channel data acquisition within distributed control topologies.

Technical Specifications

Parameter Specification
Manufacturer Emerson Process Management
Manufacturing Origin Austin, Texas
Part Number D803060X012
LocalBus Power Rating 12 VDC at 350 mA
Field Circuit Rating 5.5 VDC at 0.6 mA/channel
Terminal Block Key Position B2
Ambient Temperature Limit 0 to 60 degC
Relative Humidity Bounds 5 to 95% Non-Condensing
Enclosure Rating IP 20
Operational Shock Resistance 10g half Sinewave for 11 msec
Operational Vibration Limit 1mm Peak to Peak from 5 to 16Hz; 0.5g from 16 to 150Hz
Environmental Gaseous Protection ISA-S71.04-1985 Airborne Contaminants Class G3

Connections/Interfaces

Mechanical Alignment Component Assignment Function
Terminal Block Key Position B2 Ensures hardware compatibility between the I/O card and the specific field terminal block

Installation Guidelines

  • Field Power Disconnection: All field power supplied to the device, either at the field terminal or as bussed field power through the carrier, must be completely removed before disconnecting or removing the unit.
  • Energized Maintenance Conditions: This unit may be removed or inserted while system power is energized under the following conditions: Only one unit at a time may be removed with system power energized. It must be used with a KJ1501X1-BC1 System Dual DC/DC Power Supply operating on 24 VDC or 12 VDC input power.
  • Inductance Limitations: The primary circuit wiring inductance for input power must be less than 23 uH, or a certified supply with an open circuit voltage, Ui of 12.6 VDC and an Lo of less than 23 uH (including wire inductance) must be utilized.
  • Fuse Handling: A terminal block fuse may NOT be removed with field power energized for non-sparking circuits.
  • Hardware Adjustments: This unit contains no user serviceable parts and should not be disassembled for any reason. Calibration is not required.

Compliance and Certifications

  • ATEX Certification Number | Nemko No. 02ATEX431U |
  • ATEX Code | II 3 G EEx nL IIC T4 |
  • FM Approval | Class I Division 2 Groups A, B, C, D Hazardous Locations, Temperature Rating T4 |
  • CSA Certification | LR87534 |
  • CE Mark | Certified |
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Emerson VE4003S5B1 KJ3002X1-BG2 12P1731X082 Carte d'entrée thermocouple mV

Can this device be hot-swapped while the system is powered?

Yes, a single unit may be removed or inserted while system power is energized, provided it is used with a KJ1501X1-BC1 System Dual DC/DC Power Supply operating on 24 VDC or 12 VDC input power, and the primary circuit wiring inductance is less than 23 uH.

What are the requirements for handling terminal block fuses?

A terminal block fuse must not be removed while field power is energized for non-sparking circuits.

Does the device require regular maintenance or calibration?

No, the device contains no user serviceable parts, must not be disassembled, and does not require calibration.

Expédition express mondiale

  • Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
  • Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
  • Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats arabes unis.

Retours et garantie

  • Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d'origine scellé en usine.
  • Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.

Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).


Pour connaître l'éligibilité complète, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel Politique de remboursement et de retour .

TECHNICAL SPECIFICATIONS

Color pattern
Noir
Country of origin
États-Unis
Power source
Alimentation DC

Produits récemment consultés

Connaissances techniques

Actionneurs électriques conçus pour remplacer les fluides : tutoriel pratique

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Opérations mathématiques avec OpenPLC pour les applications d'automatisation industrielle

Cet article explique comment les systèmes PLC réalisent des opérations mathématiques de base telles que l'addition, la soustraction, la multiplication, la division, le modulo et l'exponentiation dans...

Logique booléenne avancée avec la programmation FBD PLC : applications industrielles pratiques au-delà de la logique de base

L'article explique plusieurs fonctions avancées de la logique booléenne utilisées en programmation d'automates programmables industriels (API) au-delà des opérations de base ET, OU et NON. Il aborde...

Logique booléenne en programmation PLC : comprendre les portes logiques FBD

La logique booléenne est la base de tout programme PLC. Des commandes machines simples aux systèmes d'automatisation industrielle complexes, les portes logiques déterminent comment les contrôleurs...

Guide approfondi sur les pare-feux industriels et la segmentation des réseaux OT

Les pare-feux industriels jouent un rôle crucial dans la cybersécurité OT, protégeant les réseaux PLC, DCS et SCADA grâce à la segmentation, au contrôle des entrées/sorties et à l’intégration IDS/IPS...

Guide des pinces robotiques : de la manipulation délicate à l'automatisation lourde

Les pinces robotiques modernes évoluent au-delà des mâchoires mécaniques traditionnelles. Des systèmes adhésifs inspirés des geckos aux pinces souples de qualité alimentaire, en passant par des...