Description

Engineered specifically for legacy CV-series backplane architectures, the Omron CVM1-PA208 supplies reliable, low-noise DC control power directly to the rack's system buses. This high-capacity power module accepts a wide AC input range and converts it to a highly stable 5 VDC, 8 A output, which is crucial for maintaining processor integrity and preventing backplane communication errors. The unit is optimized for heavy-duty industrial configurations where PLC modules require consistent current supply without voltage sags.

Features

  • High-current 8 A output capacity at 5 VDC to power dense I/O racks and high-performance CPUs.
  • Flexible AC input selection accommodating standard industrial line voltages.
  • Integrated RUN output relay contact for external monitoring of power supply health.
  • Robust noise filter circuitry to shield sensitive internal logic from electrical line transients.
  • Overcurrent and overvoltage protection limits to prevent downstream component damage during field faults.

Applications

  • Omron CV500, CV1000, and CV2000 PLC Rack Installations.
  • Automotive assembly line host control units.
  • Large-scale material handling and distribution systems.
  • Water treatment and chemical plant automation backplanes.

Technical Specifications

Parameter Specification
Manufacturer Omron
Model Number CVM1-PA208
Input Voltage 100 to 120 VAC / 200 to 240 VAC (selectable)
Frequency Rating 50 / 60 Hz
Output Voltage 5 VDC
Output Current 8 A
Power Consumption 150 VA
Operating Temperature 0 to 55 degC (32 to 131 degF)
Country of Origin Japan
Shipping Weight (Calculated) 1.50 kg
Package Dimensions (Calculated) 24.5 x 14.0 x 9.5 cm

Connections and Interfaces

Terminal Label Function / Circuit Assignment
AC100-120V / AC200-240V Main AC line power supply input terminals.
LG Line ground (noise filter ground) to reduce common-mode high-frequency interference.
GR Frame Ground terminal connected directly to the system grounding bar.
RUN OUT Relay contact terminals (SPST-NO) that close when the CPU is operating normally.

Alternative Models & Compatibility

The CVM1-PA208 power supply replaces standard or lower amperage modules within the CV family (such as 3 A and 5 A variants) to support system expansions containing high-density digital or analog cards. When updating backplane hardware, verify that total current consumption on the 5 VDC internal bus does not exceed the unit's 8 A output ceiling.

Application Pitfalls & Engineering Notes

Overheating in sealed, non-ventilated enclosures can lead to accelerated aging of the internal smoothing capacitors. Keep a minimum vertical spacing of 20 mm around the rack power unit to allow convective cooling. If output voltage drops below 4.75 VDC, the system watchdog will trip, halting PLC execution as a safety precaution.

Commissioning & Wiring Tips

Ensure that the Line Ground (LG) and Frame Ground (GR) terminals are wired correctly. Loop the GR terminal with a heavy, low-impedance ground strap directly to your panel plate. Leaving the GR terminal disconnected or sharing a daisy-chained ground with high-noise variable frequency drives (VFDs) can introduce electromagnetic interference, causing intermittent CPU memory corruptions.

Installation Guidelines

CRITICAL WARNING

Disconnect all incoming AC electrical power sources before handling, mounting, or wiring the terminal block. Touch hazards exist at input terminals when line power is applied. Verify the absence of voltage with a properly calibrated multimeter prior to starting system integration.

1 Align the bottom-hook mechanism of the power supply module with the designated base slot on the CV-series backplane.
2 Pivot the module smoothly upward into the backplane, pressing firmly until the top connector seat snaps completely home.
3 Secure the upper module retaining screw to the chassis to ensure mechanical grounding and guard against vibration-induced displacement.
4 Complete the electrical terminal wiring, torque terminal screws to 1.2 N-m, and apply protective terminal covers before energization.
Loading product navigation…

Does this power supply unit support auto-ranging voltage input?

No. The input voltage range is manually configured or jumper-selected at the terminal block. Ensure that your terminal connections match the 100-120 VAC or 200-240 VAC supply lines before power up.

What is the function of the RUN OUT contact?

The RUN output is a dry relay contact that closes when the internal system logic voltage is normal and the CPU executes normally. It is commonly integrated into master control or safety circuit loops.

Can I upgrade my existing CV500 power supply to this 8 Amp module?

Yes. This high-capacity module is pin-compatible with CV500, CV1000, and CV2000 backplanes, offering a robust power upgrade for configurations containing power-hungry I/O or communication cards.

Expédition express mondiale

  • Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
  • Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
  • Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats arabes unis.

Retours et garantie

  • Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d'origine scellé en usine.
  • Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.

Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).


Pour connaître l'éligibilité complète, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel Politique de remboursement et de retour .

TECHNICAL SPECIFICATIONS

Country of origin
Japon

Produits récemment consultés

Connaissances techniques

Actionneurs électriques conçus pour remplacer les fluides : tutoriel pratique

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Opérations mathématiques avec OpenPLC pour les applications d'automatisation industrielle

Cet article explique comment les systèmes PLC réalisent des opérations mathématiques de base telles que l'addition, la soustraction, la multiplication, la division, le modulo et l'exponentiation dans...

Logique booléenne avancée avec la programmation FBD PLC : applications industrielles pratiques au-delà de la logique de base

L'article explique plusieurs fonctions avancées de la logique booléenne utilisées en programmation d'automates programmables industriels (API) au-delà des opérations de base ET, OU et NON. Il aborde...

Logique booléenne en programmation PLC : comprendre les portes logiques FBD

La logique booléenne est la base de tout programme PLC. Des commandes machines simples aux systèmes d'automatisation industrielle complexes, les portes logiques déterminent comment les contrôleurs...

Guide approfondi sur les pare-feux industriels et la segmentation des réseaux OT

Les pare-feux industriels jouent un rôle crucial dans la cybersécurité OT, protégeant les réseaux PLC, DCS et SCADA grâce à la segmentation, au contrôle des entrées/sorties et à l’intégration IDS/IPS...

Guide des pinces robotiques : de la manipulation délicate à l'automatisation lourde

Les pinces robotiques modernes évoluent au-delà des mâchoires mécaniques traditionnelles. Des systèmes adhésifs inspirés des geckos aux pinces souples de qualité alimentaire, en passant par des...