The BECKHOFF EP3204-0002 EtherCAT Box is a four-channel input module designed for direct connection of resistance thermometers in industrial machine environments without control cabinets. As part of the EtherCAT Box product family, this unit features a rugged IP65, IP66, and IP67 protection rating, allowing it to be mounted directly on plant machinery close to the process sensors.

This module processes signals from various resistance sensors and potentiometers, supporting multiple sensor types including Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, and Ni1000, as well as direct resistance measurement. Sensor connection is accommodated via M12 screw-type connectors configured for two-, three-, or four-wire setups.

Communication with the control system is established via the high-speed EtherCAT protocol, linked through shielded M8 sockets. Power is distributed across the module using M8 connectors for the 24 V DC US supply, ensuring straightforward daisy-chaining and integration into decentralized automation architectures.

Features

    Four analog input channels for resistance thermometers and resistance measurement.
  • Support for multiple sensor types including Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, and resistive elements.
  • Rugged IP65/IP66/IP67 enclosure for direct machine-level mounting in harsh environments.
  • Configurable input filter variations and selectable conversion times from 2 ms to 800 ms.
  • Integrated open-circuit recognition for enhanced diagnostic reliability.
  • EtherCAT communication interface with dual shielded M8 sockets for line topology integration.

Applications

  • Decentralized temperature acquisition in machine building and factory automation systems.
  • Process temperature monitoring on conveyors, handling equipment, and packaging lines.
  • Direct machine-mounted sensor integration in environments requiring high water and dust protection.
  • Resistive position and potentiometer feedback in decentralized industrial assemblies.

Technical Specifications

General

Parameter Specification
Manufacturer BECKHOFF
Exact Model EP3204-0002
Product Type EtherCAT Box
Protocol EtherCAT
Weight approx. 165 g

Electrical and Input Data

Parameter Specification
Number of Inputs 4
Sensor Types Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (10 ohm to 1.2/4 kohm)
Measuring Range -200 to +850 degC (Pt sensors); -60 to +250 degC (Ni sensors)
Resolution 0.1 degC per digit
Measurement Error < +/-0.5 degC (Pt sensors in 4-wire connection)
Conversion Time 800 ms up to 2 ms (default approx. 85 ms)
Measuring Current typ. 0.5 mA
Nominal Voltage 24 V DC (-15 percent / +20 percent)
Current Consumption from US 120 mA
Electrical Isolation 500 V

Connections and Interfaces

Parameter Specification
Bus Interface 2 x M8 socket, shielded, screw type
Power Supply Connection Feed: 1 x M8 male socket, 4-pin; Downstream connection: 1 x M8 female socket, 4-pin
Sensor Connection Method Screw type M12 for 2-, 3-, and 4-wire connections (presetting: 2-wire)

Environmental and Approvals

Parameter Specification
Operating Temperature Range -25 to +60 degC
Storage Temperature Range -40 to +85 degC
Protection Rating IP65, IP66, IP67 (conforms to EN 60529)
Vibration and Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity and Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Approvals and Markings CE, UL, ATEX
Ex Marking II 3 G Ex nA IIC T4 Gc

Installation Guidelines

  1. Verify that the exact model EP3204-0002 matches your system design requirements and part list.
  2. Ensure all system power supplies are completely de-energized before mounting or wiring the module.
  3. Inspect the module housing, M8 bus sockets, M12 sensor connectors, and seals for any physical damage.
  4. Mount the EtherCAT Box securely onto a flat machine surface using appropriate mechanical fasteners.
  5. Connect the 24 V DC power supply feed to the designated M8 male socket and downstream connections if applicable.
  6. Wire the temperature sensors to the M12 connectors using the correct 2-, 3-, or 4-wire configuration matching your sensor type.
  7. Attach shielded EtherCAT cables to the M8 bus sockets to maintain communication integrity.
  8. Check all connections, verify potential distribution, and power on the system to perform commissioning through the control software.

FAQ

What is the primary function of the BECKHOFF EP3204-0002 EtherCAT Box?

The BECKHOFF EP3204-0002 EtherCAT Box is a decentralized 4-channel input module designed to acquire temperature and resistance measurements directly on machine frames without requiring a control cabinet.

Which sensor types are supported by the BECKHOFF EP3204-0002?

The BECKHOFF EP3204-0002 supports Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000 sensors, and general resistance measurements such as potentiometers using 2-, 3-, or 4-wire connection methods.

What environmental protection rating does the BECKHOFF EP3204-0002 feature?

The BECKHOFF EP3204-0002 features an IP65, IP66, and IP67 protection rating, making it fully protected against dust and water ingress for harsh industrial environments.

How does the BECKHOFF EP3204-0002 connect to the control network?

The BECKHOFF EP3204-0002 communicates via the EtherCAT protocol using two shielded M8 sockets for bus incoming and outgoing lines.

View all FAQs →

Quantity
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Technical knowledge

Replacing ABB DSQC 351: Controller and Network Checks

Checks to record before replacing ABB 3HNE 00006-1 DSQC 351: controller generation, X3/X5/X20/X21 wiring, DeviceNet settings, INTERBUS mapping, and LED states.

IC693CPU360 vs IC693CPU364: Ethernet and Power Budget

Compare the IC693CPU360 and IC693CPU364 by Ethernet interface, +5 VDC load, memory, rack limits, and replacement checks.

1756-OF4 Output Wrong? Check Mode, RTB, and Scaling First

A field-first diagnostic sequence for 1756-OF4 analog output problems: channel mode, removable terminal block, scaling, and controlled electrical checks.

1746-OA8 vs 1746-OA16: Output Count and Current Limits

A direct comparison of 1746-OA8 and 1746-OA16 output count, common grouping, backplane current and temperature-derated load limits.

Replacing a 1761-NET-DNI: Capture These Settings First

A field checklist for recording the 1761-NET-DNI hardware series, firmware, EDS file, DF1 settings, DeviceNet address and messaging configuration before replacement.

EL3062 vs EL3062-0030: The Input Range Changes

The EL3062 is a 0–10 V EtherCAT terminal. The EL3062-0030 is a 0–30 V variant. This checklist covers identification, scaling and commissioning.