Manufacturer: Emerson
Product No.: SE5009
Country of origin:United States
Product Type: DC to DC Power Supplies
Payment: T/T, Western Union
Weight: 850g
Dimensions: 85 mm x 210 mm x 140 mm (W x H x D)
Shipping port: Xiamen
Warranty: 12 months
The Emerson SE5009 is a modular 24VDC system power supply designed for the DeltaV S-series distributed control platform. Connecting directly to 24 VDC plant bulk power, the unit provides localized system power to DeltaV controllers and associated I/O interfaces without requiring external cabling. The module fits into DeltaV power/controller carriers to energize internal power buses, delivering 5 VDC power to the controller and up to 8.0 A of 12 VDC power to the I/O subsystem. Featuring load-sharing and modular expansion, the SE5009 supports system redundancy and maintains steady output power under varying input voltage conditions.
| Description | Model Number |
|---|---|
| 24VDC System Power Supply | SE5009 |
| Parameter | Specification |
|---|---|
| Manufacturer | Emerson |
| Model | SE5009 |
| Series | DeltaV S-series |
| Product Type | DC to DC System Power Supply |
| Input Voltage | 24 VDC +/- 20% at 6.1 A |
| Inrush Current | 20 A peak maximum for 5 ms over 24 VDC input range |
| Output Power Rating (-40 to 60 degC) | +12 VDC at 8.0 A, +5 VDC at 2.0 A (10 W total combined +5 VDC outputs) |
| Output Power Rating (60 to 70 degC) | +12 VDC at 6.0 A, +5 VDC at 2.0 A (10 W total combined +5 VDC outputs) |
| Input Protection | Internally fused, non-replaceable |
| Overvoltage Protection | Output protected at 110% to 120% |
| Hold-up Time | Output remains within 5% of nominal at full load and minimum input for 5 ms |
| Operating Temperature | -40 to 60 degC (-40 to 140 degF) without derating; 60 to 70 degC (140 to 158 degF) with derating |
| Storage Temperature | -40 to 70 degC (-40 to 158 degF) |
| Relative Humidity | 5 to 95%, non-condensing |
| Airborne Contaminants | ISA-S71.04-1985 airborne contaminants class G3 |
| Shock | 10 g 1/2-sine wave for 11 ms |
| Vibration | 1 mm peak-to-peak from 5 Hz to 13.2 Hz, 0.7 g from 13.2 Hz to 150 Hz |
| Mounting | Either slot of 2-wide power/controller carrier, power slot of VerticalPlus 4-wide carrier, any slot of 4-wide power carrier |
| System Prerequisites | DeltaV v11.3 or later; compatible with S-series Horizontal carriers |
| Connector Pin | Function |
|---|---|
| Primary Power | DC input, 2-wire |
| Alarm Contact | 2-wire normally open relay (2.0 A at 30 VDC, 2.0 A at 250 VAC) |