General Electric

General Electric IC697ALG230 Series 90-70 Analog Input Base Converter Module

SKU IC697ALG230

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: General Electric

  • Product No.: IC697ALG230

  • Country of origin:United States

  • Product Type: Analog Input Module

  • Payment: T/T, Western Union

  • Weight: 450g

  • Dimensions: 15.0 x 3.5 x 14.2 cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The General Electric IC697ALG230 is an eight-channel high-level analog input base converter module designed for the Series 90-70 programmable logic controller platform. Serving as the primary interface in a high-level analog input subsystem, this module processes unipolar and bipolar signals—including standard ranges up to plus or minus 10 VDC and 4 to 20 mA current loops—converting them via a 14-bit A/D core into 16-bit signed integer values for the VME backplane CPU.

Equipped with differential inputs and on-board load resistors, the IC697ALG230 provides superior common-mode noise rejection and supports individual channel user scaling without the need for physical jumpers or DIP switches. It acts as the master controller for up to seven daisy-chained expander modules, allowing scalable system configurations of up to 120 total analog inputs within the PLC rack architecture.

Features

  • Features 8 differential input channels individually configurable for voltage or current measurements
  • Supports unipolar and bipolar inputs up to plus or minus 10 VDC and 4 to 20 mA loops
  • Provides 14-bit basic A/D resolution enhanced via oversampling and averaging techniques
  • Jumperless configuration managed entirely through programming software utilities
  • Supports expansion bus architecture to interface up to 7 expander modules for a 120-input maximum subsystem
  • Integrated diagnostic features including overrange, underrange, open-wire, and alarm comparator functions

Applications

  • High-density analog sensor signal conditioning in industrial control loops
  • Remote rack analog data acquisition expansion for Series 90-70 automation systems
  • Precision closed-loop process variable monitoring and threshold alarm processing
  • Multi-channel voltage and current telemetry integration in heavy industrial environments

Technical Specifications

Parameter Specification
Brand General Electric
Series Series 90-70
Catalog Number IC697ALG230
Product Type Analog Input Base Converter Module
Number of Channels 8 Differential Inputs
Input Voltage Ranges -10V to +10V, 0 to +10V, -5V to +5V, 0 to +5V
Input Current Ranges 4 to 20 mA (using internal 250 ohm precision shunt resistors)
Resolution 14-bit basic (1 part in 16384), 16-bit scaled representation
Update Rate 2.4 ms to 2.8 ms maximum for all 8 base channels
Input Impedance Greater than 10 Megohms at DC (Voltage); 250 ohms, 0.1 percent shunt (Current)
Isolation Optically isolated from VME backplane
Backplane Power Requirements +5 VDC at 0.8A (4 W) maximum
Country of Origin United States

Connections / Interfaces

  • Removable 40-terminal front-mount connector block for field instrumentation wiring
  • Terminals 35 through 40 dedicated to the analog expansion bus for daisy-chaining expander modules
  • Physical mechanical keying system to prevent incorrect module insertion in rack slots

Compliance and Certifications

  • Designed to meet applicable Series 90-70 system standards
  • CE compliant for industrial electromagnetic compatibility
  • UL listed industrial control equipment

FAQ

How many input channels does the IC697ALG230 support?

The IC697ALG230 base converter module provides 8 differential input channels, which can be individually configured for either voltage or current signals.

Can the IC697ALG230 be expanded to accept more inputs?

Yes, up to seven expander modules (such as the IC697ALG440 or IC697ALG441) can be daisy-chained off the base converter module, expanding the total subsystem capacity up to 120 analog inputs.

What is the update rate of the base converter channels?

The base converter inputs are updated sequentially approximately every 2.4 ms to 2.8 ms for all eight channels.

Are physical jumpers required to configure input ranges?

No jumpers or DIP switches are required on the module; all input ranges, scaling, and operational parameters are configured through the programming software.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

General Electric IC697ALG230 Series 90-70 Analog Input Base Converter Module

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 14 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Technical knowledge

ABB PM891K01 Replacement: Check Redundancy Before Ordering

ABB PM891K01 article 3BSE053241R1 is the non-redundant AC 800M processor kit. Use this field checklist before replacement.

ABB TP853 Replacement Checks for CI853/CI855/CI857/CI861

Replacement checks for ABB TP853 3BSE018126R1: identify the installed CI853, CI855, CI857, or CI861 interface, record wiring, and verify communication after installation.

5069-L330ERMS2 Startup Checks: RTBs, I/O, and Motion Limits

Engineering checks for the Allen-Bradley 5069-L330ERMS2: controller capacity, separate RTB kits, local I/O limits, network-node limits, and motion-axis count.

Replacing ABB DSQC 351: Controller and Network Checks

Checks to record before replacing ABB 3HNE 00006-1 DSQC 351: controller generation, X3/X5/X20/X21 wiring, DeviceNet settings, INTERBUS mapping, and LED states.

IC693CPU360 vs IC693CPU364: Ethernet and Power Budget

Compare the IC693CPU360 and IC693CPU364 by Ethernet interface, +5 VDC load, memory, rack limits, and replacement checks.

1756-OF4 Output Wrong? Check Mode, RTB, and Scaling First

A field-first diagnostic sequence for 1756-OF4 analog output problems: channel mode, removable terminal block, scaling, and controlled electrical checks.