HIMA

HIMA HIMatrix F2 DO 8 01 Safety-Related Remote I/O Module

SKU F2DO801

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: HIMA

  • Product No.: F2DO801

  • Country of origin:Germany

  • Product Type: Safety-Related Remote I/O Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 1300g

  • Dimensions: 114 mm x 207 mm x 86 mm (H x W x D without plug)

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The HIMA F2 DO 8 01 (also designated as F2DO801) is a compact, safety-related remote I/O unit housed in a metal enclosure and featuring 8 safety-related relay outputs. Designed for safety shutdown applications up to SIL 3, the F2 DO 8 01 extends the I/O capacity of HIMax and HIMatrix controllers over safeethernet communication.

Each output channel on the F2 DO 8 01 (F2DO801) incorporates two safety relays with forcibly guided contacts and one standard relay, providing potential-free normally open contact operation. The module operates on 24 VDC power and features an integrated 2-port Ethernet switch for network integration.

Features

  • HIMA F2 DO 8 01 (F2DO801) contains 8 safety-related relay outputs with potential-free normally open contacts.
  • Integrated Ethernet switch with two RJ-45 ports supporting safeethernet communication at 10/100 Mbit/s.
  • Relay outputs feature forcibly guided safety contacts and individual internal 3.15 A fuses.
  • Compatible with SILworX (OS version 7 and beyond) and ELOP II Factory (OS versions prior to 7).
  • Compact metal enclosure designed for 35 mm DIN rail mounting with IP20 protection class.
  • Certified for installation in Ex-Zone 2 hazardous locations.
  • Onboard diagnostic LED indicators for power supply, processor status, communication, and individual output channels.

Applications

  • Safety shutdown systems in process automation
  • Remote I/O expansion for HIMax and HIMatrix safety controllers
  • Hazardous area control applications requiring Ex-Zone 2 compliance

Ordering Information

Designation Description Part No.
F2 DO 8 01 Remote I/O with 8 relay outputs up to 250 VAC / 250 VDC, operating temperature 0...+60 degC, for ELOP II Factory programming tool 98 2200407
F2 DO 8 01 SILworX Remote I/O with 8 relay outputs up to 250 VAC / 250 VDC, operating temperature 0...+60 degC, for SILworX programming tool 98 2200481

Technical Specifications

Parameter Specification
Manufacturer HIMA Paul Hildebrandt GmbH + Co KG
Response Time >= 20 ms
Ethernet Interfaces 2 x RJ-45, 10/100BaseT (100 Mbit/s) with integrated switch
Operating Voltage 24 VDC (-15%...+20%, w_ss <= 15%) from SELV/PELV power supply
Current Input max. 0.6 A
External Fuse 10 A time-lag
Back-up Battery None
Operating Temperature 0 degC to +60 degC
Storage Temperature -40 degC to +85 degC
Type of Protection IP20
Dimensions (without plug) Width: 207 mm, Height: 114 mm, Depth: 86 mm
Weight 1.3 kg
Relay Types per Channel 2 safety relays with forcibly guided contacts, 1 standard relay
Number of Relay Outputs 8 potential-free normally open contacts
Switching Voltage >= 5 V, <= 250 VAC / 250 VDC
Switching Current >= 10 mA, <= 3 A (internally fused with 3.15 A, breaking capacity 100 A)
AC Switching Capacity (UL) 250 VAC at 6 A
AC Switching Capacity (TUV) max. 250 VA (cos phi >= 0.5) / max. 625 VA (cos phi = 1) at max. 250 VAC
DC Switching Capacity (UL) 24 VDC at 1 A with ohmic load
DC Switching Capacity (TUV) up to 30 VDC: max. 90 W (3.5 A); up to 70 VDC: max. 22 W (0.315 A); up to 127 VDC: max. 25 W (0.25 A); up to 250 VDC: max. 40 W (0.16 A)
Contact Material Silver alloy
Switching Time approx. 30 ms
Reset Time approx. 10 ms
Bounce Time approx. 15 ms
Mechanical Life >= 3 x 10^6 switching operations
Electrical Life >= 2.5 x 10^5 switching operations at ohmic full load (<= 0.1 ops/sec)

Connections/Interfaces

Connector Pin Function
Terminal 1 DO1 Contact 1, terminal A
Terminal 2 DO1 Contact 1, terminal B
Terminal 3 DO2 Contact 2, terminal A
Terminal 4 DO2 Contact 2, terminal B
Terminal 5 DO3 Contact 3, terminal A
Terminal 6 DO3 Contact 3, terminal B
Terminal 7 DO4 Contact 4, terminal A
Terminal 8 DO4 Contact 4, terminal B
Terminal 9 DO5 Contact 5, terminal A
Terminal 10 DO5 Contact 5, terminal B
Terminal 11 DO6 Contact 6, terminal A
Terminal 12 DO6 Contact 6, terminal B
Terminal 13 DO7 Contact 7, terminal A
Terminal 14 DO7 Contact 7, terminal B
Terminal 15 DO8 Contact 8, terminal A
Terminal 16 DO8 Contact 8, terminal B

Installation Guidelines

  • Mount the module on a standard 35 mm DIN rail within a protective enclosure.
  • Provide 24 VDC power from a SELV or PELV power supply unit with safe isolation according to IEC 61131-2, protected by an external 10 A time-lag fuse.
  • For Ex-Zone 2 installations, mount inside an enclosure achieving at least IP54 protection according to EN 60529 and capable of dissipating heat (power dissipation 18 W to 46 W).
  • When connecting DC switching voltages, fit an external fuse rated for the maximum permissible current in the contact circuit.
  • Use double or reinforced insulated cabling when switching voltages higher than SELV or PELV.
  • Ensure electrostatic discharge protective measures are observed, including using an ESD wrist strap during installation or replacement.

Compliance and Certifications

  • CE: EMC, ATEX Zone 2 (Directive 94/9/EC)
  • TUV: IEC 61508 Parts 1-7:2000 up to SIL 3, IEC 61511:2004, EN 954-1:1996 up to Cat. 4
  • TUV ATEX: 94/9/EG, EN 1127-1, EN 61508
  • UL: ANSI/UL 508, NFPA 70 - Industrial Control Equipment, CSA C22.2 No.142, UL 1998, NFPA 79, IEC 61508
  • FM Approvals: Class I, DIV 2, Groups A, B, C and D; Class 3600; Class 3611; Class 3810; CSA C22.2 No 142; CSA C22.2 No 213

FAQ

What is the primary function of the module?

The module operates as a safety-related remote I/O unit that expands the output capabilities of HIMax and HIMatrix controllers over safeethernet using 8 digital relay channels.

What operating voltage is required to power the device?

The device requires a nominal operating voltage of 24 VDC (-15%...+20%) from a power supply unit with safe isolation meeting SELV or PELV standards.

What safety integrity levels is the communication module certified for?

The module is certified by TÜV for safety-related applications up to SIL 3 according to IEC 61508 and IEC 61511, Category 4 according to EN 954-1, and PL e according to EN ISO 13849-1.

What happens to the outputs if a fault is detected in the unit?

If a faulty signal or internal fault is detected, the affected channel or all digital output channels switch to the safe de-energized state, and the FAULT LED is activated.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

HIMA HIMatrix F2 DO 8 01 Safety-Related Remote I/O Module

Quantity
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 3
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Yellow
Country of origin
Germany
Power source
DC Power

Technical knowledge

Commissioning PLX32-EIP-MBTCP: Subnets, Registers, and RPI

A commissioning checklist for the ProSoft PLX32-EIP-MBTCP covering subnet separation, register contracts, EtherNet/IP timing, failure tests and replacement records.

Diagnosing IC693MDL916 Relay Outputs Before Module Replacement

A field checklist for IC693MDL916 relay commands, terminal blocks, load current, switching rate and contact-side measurements.

Troubleshooting Beckhoff KL1512 Counter Inputs and Mapping

A field checklist for KL1512 signal thresholds, counter direction, process data and the KL1512-to-KS1512 wiring difference.

Troubleshooting Beckhoff EPP2008-0001 Output Faults

A field checklist for EPP2008-0001 current limits, supply voltage, channel LEDs, connector coding and load-related output faults.

Moving TwinCAT 3 Licenses with C9900-L100: Build and Device Checks

Before moving a TwinCAT 3 license with a Beckhoff C9900-L100, verify the TwinCAT build, XML device description, exact order code and cabinet limits.

Replacing a Beckhoff EL4032: Wiring and Output Checks

A field checklist for replacing a Beckhoff EL4032, covering the ±10 V load, terminal map, power contacts, EtherCAT state, and watchdog behavior.