Honeywell

Honeywell FC-SAI-1620M Safe High-Density Analog Input Module

SKU FC-SAI-1620

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Honeywell

  • Product No.: FC-SAI-1620

  • Country of origin:United States

  • Product Type: Analog input module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 350g

  • Dimensions: 20 x 130 x 190 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The Honeywell FC-SAI-1620M is a conformal-coated, safe high-density analog input module engineered for high-integrity process safeguarding and critical automation applications within the Honeywell Safety Manager system platform. Operating on a 24 Vdc power supply, this module provides 16 dedicated analog input channels designed to interface with 0(4)–20 mA field transmitters and process instrumentation. It plays a key role in acquiring analog process variables and routing signal data over the internal Safety Manager IO Bus directly to the Quad Processor Pack (QPP) for high-integrity safety logic processing.

Designed to meet stringent functional safety standards up to SIL3 per IEC 61508, the FC-SAI-1620M executes continuous internal diagnostic self-tests within a defined Diagnostic Test Interval (DTI). Its conformal coating protects the internal Eurocard circuit board against harsh industrial environments, ensuring reliable long-term performance in Emergency Shutdown (ESD), Fire and Gas (F&G) detection, and Burner Management Systems (BMS).

Features

  • Conformal Coating: Formulated with protective coating (FC prefix) to resist environmental contaminants, moisture, and corrosive airborne elements in harsh plant environments.
  • High-Density Channel Layout: Features 16 safe analog input channels within a compact 3U / 4HP Eurocard form factor to maximize cabinet rack space.
  • SIL3 Functional Integrity: Fully certified for use in safety instrumented functions up to Safety Integrity Level 3 in both single and Quadruple Modular Redundant (QMR) architectures.
  • Comprehensive Self-Diagnostics: Conducts automatic, background diagnostic testing of internal circuitry and signal paths within the Diagnostic Test Interval (DTI) to detect and isolate hardware anomalies safely.
  • Field Termination Assembly Integration: Connects seamlessly to external Field Termination Assemblies (such as TSAI-1620m or TSHART-1620m) using standard System Interconnection Cables (FS-SIC-0001).
  • Hot-Swappable Subsystem Architecture: Integrates into the Safety Manager IO chassis backplane via standard 32-pin DIN 41612F connectors with key coding to prevent improper module insertion.

Applications

  • Process Safeguarding & ESD: Monitors critical process instrumentation (pressure, temperature, flow, level) for Emergency Shutdown loops.
  • Fire & Gas (F&G) Monitoring: Interfaces with analog gas and flame detectors in hydrocarbon processing and off-shore facilities.
  • Burner Management Systems (BMS): Safe tracking of fuel pressures, airflow, and flame intensity signals in boiler and furnace control applications.
  • Turbine & Compressor Protection: Continuous monitoring of operating variables to prevent surge, overpressure, or mechanical overspeed conditions.

Technical Specifications

Parameter Specification
Manufacturer Honeywell
Model FC-SAI-1620M
Part Number Prefix FC (Conformal Coated)
System Platform Safety Manager
Module Type Safe High-Density Analog Input Module
Number of Channels 16 channels
Nominal Voltage 24 Vdc
Signal Range 0–20 mA / 4–20 mA
Safe Failure Fraction (SFF) ≥ 99%
Safety Integrity Level Up to SIL3 (IEC 61508 / ISA S84.01)
Module Form Factor Eurocard (100 x 160 mm / 3.94 x 6.30 in)
Panel Dimensions Height: 3U (3 HE), Width: 4HP (4 TE)
Connector Type 32-pin DIN 41612F connector
Operating Temperature -5 degC to 70 degC (14 degF to 158 degF) ambient
Storage Temperature -25 degC to 80 degC (-13 degF to 176 degF)
Relative Humidity 5% to 95%, non-condensing
Vibration Tolerance IEC 60068-2-6; 1 G at 57 Hz to 150 Hz; 0.075 mm from 10 Hz to 57 Hz
Shock Resistance IEC 60068-2-27; 15 G for 11 ms, 3 axes

Connections / Interfaces

Connection Point Description
Backplane Connector Standard 32-pin DIN 41612F Eurocard interface with mechanical keying
System Cable Interface Connects to Field Termination Assembly (TSAI-1620m / TSHART-1620m) via FS-SIC-0001 System Interconnection Cable
Primary Bus Link Communicates with the Control Processor via the Safety Manager horizontal and vertical IO Bus

Installation Guidelines

  1. Pre-Installation Inspection: Verify that the module model code (FC-SAI-1620M) matches project drawings and check the conformal coating for any physical damage prior to installation.
  2. Power Off Rack Section: Ensure supply power to the target slot or chassis segment is turned off or isolated according to plant safety procedures before inserting non-redundant hardware.
  3. Align and Seat Module: Carefully align the Eurocard edges with the card guides in the 3U slot of the IOCHAS chassis. Push firmly until the 32-pin DIN 41612F connector seats completely into the backplane.
  4. Secure Fasteners: Tighten top and bottom retaining screws on the front panel to guarantee proper grounding and mechanical stability under vibration.
  5. Cabling to FTA: Connect the System Interconnection Cable (FS-SIC-0001) from the rear backplane port to the corresponding Field Termination Assembly (TSAI-1620m or TSHART-1620m).

Configuration / Commissioning / Replacement

Configuration Guidelines

  • Define channel parameters and signal ranges (0–20 mA or 4–20 mA) in the Safety Builder software environment using Point Configurator.
  • Configure channel-specific fault reaction states (e.g., Top Scale, Bottom Scale, Scan, or Hold) according to loop safety requirements.

Commissioning Recommendations

  • Perform field signal loop checks from the transmitter through the FTA to the Safety Builder station to verify live reading accuracy.
  • Validate diagnostic trip thresholds and verify that input discrepancies trigger appropriate alarms on the station HMI without tripping operational process loops prematurely.

Replacement Recommendations

  • Parameter Backup: Confirm the project logic and I/O map database are fully backed up in Safety Builder prior to replacing an existing module.
  • Hardware Matching: Ensure the replacement module carries the conformal-coated FC-SAI-1620M designation to maintain environmental resistance ratings in critical areas.

Compliance and Certifications

  • Functional Safety: Certified by TÜV to IEC 61508 Parts 1–7 (SIL3 capable) and ANSI/ISA S84.01.
  • Standard ESD/ESD: Compliant with DIN V VDE 19250, DIN V VDE 0801, and UL 1998 / UL 508.
  • Hazardous Locations: CSA certified (C22.2 No. 142-M1987) and FM 3611 Class I, Division 2 compliant.
  • CE Compliance: Conforms to European Directives 89/336/EEC (EMC) and 73/23/EEC (Low Voltage Directive).
  • EMC Immunity: Tested to IEC 61000-4-2 (ESD Level 4), IEC 61000-4-3 (Radiated), IEC 61000-4-4 (Burst Level 3), and IEC 61000-4-5 (Surge Level 3).

FAQ

What is the primary function of the Honeywell FC-SAI-1620M analog input module?

The Honeywell FC-SAI-1620M is a high-density, 16-channel safe analog input module designed to interface 0(4)–20 mA field signals with the Honeywell Safety Manager system for SIL3 safety-critical control and process safeguarding applications.

What does the 'FC' prefix indicate in the Honeywell FC-SAI-1620M model number?

The 'FC' prefix designates that the Honeywell FC-SAI-1620M module features conformal coating on its electronic assemblies, providing enhanced resistance against humidity, moisture, and corrosive atmospheric contaminants compared to non-coated 'FS' models.

Which Field Termination Assemblies (FTAs) are compatible with the Honeywell FC-SAI-1620M?

The Honeywell FC-SAI-1620M connects to field wiring via dedicated Field Termination Assemblies, such as the TSAI-1620m for standard 0(4)–20 mA signals or the TSHART-1620m for HART-pass-through applications, using system interconnection cables.

What happens if a channel fault is detected on the Honeywell FC-SAI-1620M?

When an internal or signal path fault is detected during continuous self-testing, the Honeywell FC-SAI-1620M isolates the affected signal and sets the channel to its user-configured fault reaction state, such as Top Scale, Bottom Scale, Scan, or Hold.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell FC-SAI-1620M Safe High-Density Analog Input Module

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 3
Only 3 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Green
Country of origin
United States
Power source
DC Power

Technical knowledge

Replacing a Beckhoff EL4032: Wiring and Output Checks

A field checklist for replacing a Beckhoff EL4032, covering the ±10 V load, terminal map, power contacts, EtherCAT state, and watchdog behavior.

Replacing Yokogawa AAI835: Wiring and Barrier Checks Before Swap

Before replacing a Yokogawa AAI835, verify the 4-in/4-out channel map, power-loss loop behavior, barrier type, output load, cable, and redundancy.

ABB PM891K01 Replacement: Check Redundancy Before Ordering

ABB PM891K01 article 3BSE053241R1 is the non-redundant AC 800M processor kit. Use this field checklist before replacement.

ABB TP853 Replacement Checks for CI853/CI855/CI857/CI861

Replacement checks for ABB TP853 3BSE018126R1: identify the installed CI853, CI855, CI857, or CI861 interface, record wiring, and verify communication after installation.

5069-L330ERMS2 Startup Checks: RTBs, I/O, and Motion Limits

Engineering checks for the Allen-Bradley 5069-L330ERMS2: controller capacity, separate RTB kits, local I/O limits, network-node limits, and motion-axis count.

Replacing ABB DSQC 351: Controller and Network Checks

Checks to record before replacing ABB 3HNE 00006-1 DSQC 351: controller generation, X3/X5/X20/X21 wiring, DeviceNet settings, INTERBUS mapping, and LED states.