Schneider Electric 140AVI03000 Modicon Quantum Multirange Analog Input Module

Quantity

Product Description

Description

The Schneider Electric 140AVI03000 is an 8-channel differential multirange analogue input module engineered for the Modicon Quantum automation platform. It provides reliable acquisition and high-accuracy processing of continuous analog field signals, functioning as a primary signal conditioning interface between process transmitters, instrumentation, and the Quantum controller backplane.

Designed for versatile analog signal integration, the 140AVI03000 supports both unipolar and bipolar current and voltage configurations. It handles standard current loops including 0 to 20 mA and bipolar 20 mA, alongside voltage spans across +/-10 V, +/-5 V, 0 to 10 V, and 0 to 5 V. Featuring a 16-bit analog-to-digital resolution and built-in single-pole low-pass filtering (-3 dB at 847 Hz +/- 20%), the module delivers stable digitised process measurement with minimal electrical noise interference.

The module incorporates robust galvanic protection to maintain signal integrity in demanding industrial electrical environments, providing 500 Vrms AC / 750 V DC isolation between channels and the backplane bus, as well as 135 Vrms AC / 200 V DC channel-to-channel isolation. An addressing requirement of 9 input words enables complete diagnostic oversight, including fault detection for broken wires on 4...20 mA loops and scale overtaking on 1...5 V signals.

Features

  • 8 differential analog channels supporting both unipolar and bipolar voltage and current signals.
  • 16-bit resolution across all standard operating ranges for high-precision measurement.
  • Integrated single-pole low-pass filter (-3 dB at 847 Hz +/- 20%) to mitigate high-frequency signal noise.
  • Comprehensive isolation ratings: 500 Vrms AC (750 V DC) bus-to-channel and 135 Vrms AC (200 V DC) channel-to-channel.
  • Built-in loop diagnostics capable of detecting broken wires (4...20 mA) and scale overtaking (1...5 V).
  • Fast 10 ms cycle update time for real-time process monitoring.
  • Front-panel LED diagnostic array providing immediate indication of bus active status, external faults, channel active states, and channel fault conditions.

Applications

  • Interfacing process transmitters (flow, pressure, level, temperature) with Modicon Quantum control systems.
  • Bipolar and unipolar voltage or current measurement in continuous process automation.
  • Industrial monitoring applications requiring channel-to-channel electrical isolation to eliminate ground loops.
  • Data acquisition in retrofit, expansion, or maintenance projects for Modicon Quantum automation racks.

Technical Specifications

General

Parameter Specification
Manufacturer Schneider Electric
Brand Modicon
Platform Modicon Quantum Automation Platform
Exact Model 140AVI03000
Product Type Analogue Input Module
Module Format Standard
Addressing Requirement 9 Input Words

Input Characteristics

Parameter Specification
Number of Channels 8
Input Topology Differential
Input Ranges (Current) Unipolar: 0...20 mA; Bipolar: 20 mA
Input Ranges (Voltage) Unipolar: 0...10 V, 0...5 V; Bipolar: +/- 10 V, +/- 5 V
Resolution 16 bits (+/- 10 V, +/- 5 V, 0...10 V, 0...5 V, 0...20 mA, 20 mA)
Linear Measuring Range (Input Range) x 1.024 V / (Input Range) x 1.024 mA
Absolute Maximum Input 50 V DC, 25 mA
Input Impedance > 20 Ohm (voltage range) / 250 MOhm +/- 0.03%
Filter Type Single Pole Low Pass (-3 dB at 847 Hz +/- 20%)
Fault Detection Broken wire (4...20 mA), Overtaking scale (1...5 V)

Performance & Accuracy

Parameter Specification
Update Time 10 ms
Absolute Accuracy Error +/- 0.03%, +/- 0.05% of full scale maximum
Linearity Error +/- 0.008%
Accuracy Drift vs Temperature +/- 0.0015% of full scale/degC, <= 0.004% of full scale/degC
Common Mode Rejection > -80 dB at 60 Hz

Electrical & Power

Parameter Specification
Bus Current Requirement 280 mA
Power Dissipation 2.2 W
Isolation (Channel to Bus) 500 Vrms AC (60 s), 750 V DC
Isolation (Channel to Channel) 135 Vrms AC, 200 V DC

Mechanical & Environmental

Parameter Specification
Net Weight 0.3 kg (0.7 lb)
Operating Temperature 0 to 60 degC (32 to 140 degF)
Storage Temperature -40 to 85 degC (-40 to 185 degF)
Relative Humidity 95% without condensation
Operating Altitude <= 5000 m (16404.2 ft)
Electrostatic Discharge Resistance 4 kV contact (IEC 801-2), 8 kV on air (IEC 801-2)
Electromagnetic Field Resistance 9.1 V/m (10 V/m) 80...1000 MHz (IEC 801-3)

Connections / Interfaces

Local Status Indicators

Indicator Color Function
Active LED Green Bus communication is present
External Fault LED Red External fault detected
Channel Status LEDs (8x) Green Individual channel turned on
Channel Fault LEDs (8x) Red Individual channel fault detected

Installation Guidelines

  1. Safety Precaution: Disconnect all system power and field transmitter wiring prior to mounting, wiring, or servicing the module to prevent electrical shock or equipment damage.
  2. Rack Insertion: Align the 140AVI03000 with the designated slot on the Modicon Quantum backplane rack. Firmly seats the module until the locking tabs snap into place.
  3. Wiring Connections: Wire field inputs to the appropriate terminal block following recommended polarity and channel assignments. Use shielded twisted-pair cabling for analog signal lines to minimize ambient noise.
  4. Shield Grounding: Connect cable shields to a single-point protective earth ground near the cabinet entry to prevent ground potential loops across isolated channels.
  5. Power Verification: Confirm backplane power availability matches the 280 mA bus current requirement before powering up the rack.

Configuration / Commissioning / Replacement

  • Software Setup: Configure module parameters within Unity Pro or Concept software, assigning the required 9 input words and specifying input ranges (current vs. voltage, unipolar vs. bipolar) per channel.
  • Loop Diagnostics Verification: Test fault detection features by checking broken wire responses on 4...20 mA channels and scale limit detection on 1...5 V spans.
  • Hot-Swapping / Replacement: Ensure system hot-swap procedures are followed if replacing the module under live rack power. Disconnect field terminal connectors, release backplane clips, insert the replacement 140AVI03000, and reattach the terminal block. Verify that the green Active LED turns on, indicating successful bus communications.

Compliance and Certifications

  • Standards: UL 508, CSA C22.2 No 142
  • Certifications: FM Class 1 Division 2, cUL, CE
  • Directives: EU RoHS Directive Compliant
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
FAQ
What is the function of the Schneider Electric 140AVI03000 module?
The Schneider Electric 140AVI03000 is an 8-channel differential multirange analog input module designed for the Modicon Quantum automation platform. It processes bipolar and unipolar current and voltage signals from field sensors with 16-bit resolution for the PLC controller.
What input ranges are supported by the 140AVI03000?
The 140AVI03000 analog input module supports current ranges of 0...20 mA and bipolar 20 mA, as well as voltage ranges including 0...5 V, 0...10 V, +/- 5 V, and +/- 10 V.
Does the 140AVI03000 provide channel-to-channel isolation?
Yes, the Schneider Electric 140AVI03000 provides 135 Vrms AC / 200 V DC channel-to-channel isolation, as well as 500 Vrms AC / 750 V DC isolation between the channels and the Quantum backplane bus.
How many words does the 140AVI03000 require in the PLC addressing table?
The Schneider Electric 140AVI03000 requires 9 input words in the Quantum PLC controller memory addressing table for data transfer and diagnostic signaling.
Reviews

140AVI03000

Stock &amp; lead time on request

Call
1 of 1

Schneider Electric 140AVI03000 Modicon Quantum Multirange Analog Input Module

Only 8 item(s) left in stock
  • Manufacturer: Schneider Electric

  • Product No.: 140AVI03000

  • Country of origin:France

  • Product Type: Analog Input Modules

  • Payment: T/T, Western Union

  • Weight: 1010g

  • Dimensions: 16.50cm x 31cm x 4.5cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

The Schneider Electric 140AVI03000 is an 8-channel differential multirange analogue input module engineered for the Modicon Quantum automation platform. It provides reliable acquisition and high-accuracy processing of continuous analog field signals, functioning as a primary signal conditioning interface between process transmitters, instrumentation, and the Quantum controller backplane.

Designed for versatile analog signal integration, the 140AVI03000 supports both unipolar and bipolar current and voltage configurations. It handles standard current loops including 0 to 20 mA and bipolar 20 mA, alongside voltage spans across +/-10 V, +/-5 V, 0 to 10 V, and 0 to 5 V. Featuring a 16-bit analog-to-digital resolution and built-in single-pole low-pass filtering (-3 dB at 847 Hz +/- 20%), the module delivers stable digitised process measurement with minimal electrical noise interference.

The module incorporates robust galvanic protection to maintain signal integrity in demanding industrial electrical environments, providing 500 Vrms AC / 750 V DC isolation between channels and the backplane bus, as well as 135 Vrms AC / 200 V DC channel-to-channel isolation. An addressing requirement of 9 input words enables complete diagnostic oversight, including fault detection for broken wires on 4...20 mA loops and scale overtaking on 1...5 V signals.

Features

  • 8 differential analog channels supporting both unipolar and bipolar voltage and current signals.
  • 16-bit resolution across all standard operating ranges for high-precision measurement.
  • Integrated single-pole low-pass filter (-3 dB at 847 Hz +/- 20%) to mitigate high-frequency signal noise.
  • Comprehensive isolation ratings: 500 Vrms AC (750 V DC) bus-to-channel and 135 Vrms AC (200 V DC) channel-to-channel.
  • Built-in loop diagnostics capable of detecting broken wires (4...20 mA) and scale overtaking (1...5 V).
  • Fast 10 ms cycle update time for real-time process monitoring.
  • Front-panel LED diagnostic array providing immediate indication of bus active status, external faults, channel active states, and channel fault conditions.

Applications

  • Interfacing process transmitters (flow, pressure, level, temperature) with Modicon Quantum control systems.
  • Bipolar and unipolar voltage or current measurement in continuous process automation.
  • Industrial monitoring applications requiring channel-to-channel electrical isolation to eliminate ground loops.
  • Data acquisition in retrofit, expansion, or maintenance projects for Modicon Quantum automation racks.

Technical Specifications

General

Parameter Specification
Manufacturer Schneider Electric
Brand Modicon
Platform Modicon Quantum Automation Platform
Exact Model 140AVI03000
Product Type Analogue Input Module
Module Format Standard
Addressing Requirement 9 Input Words

Input Characteristics

Parameter Specification
Number of Channels 8
Input Topology Differential
Input Ranges (Current) Unipolar: 0...20 mA; Bipolar: 20 mA
Input Ranges (Voltage) Unipolar: 0...10 V, 0...5 V; Bipolar: +/- 10 V, +/- 5 V
Resolution 16 bits (+/- 10 V, +/- 5 V, 0...10 V, 0...5 V, 0...20 mA, 20 mA)
Linear Measuring Range (Input Range) x 1.024 V / (Input Range) x 1.024 mA
Absolute Maximum Input 50 V DC, 25 mA
Input Impedance > 20 Ohm (voltage range) / 250 MOhm +/- 0.03%
Filter Type Single Pole Low Pass (-3 dB at 847 Hz +/- 20%)
Fault Detection Broken wire (4...20 mA), Overtaking scale (1...5 V)

Performance & Accuracy

Parameter Specification
Update Time 10 ms
Absolute Accuracy Error +/- 0.03%, +/- 0.05% of full scale maximum
Linearity Error +/- 0.008%
Accuracy Drift vs Temperature +/- 0.0015% of full scale/degC, <= 0.004% of full scale/degC
Common Mode Rejection > -80 dB at 60 Hz

Electrical & Power

Parameter Specification
Bus Current Requirement 280 mA
Power Dissipation 2.2 W
Isolation (Channel to Bus) 500 Vrms AC (60 s), 750 V DC
Isolation (Channel to Channel) 135 Vrms AC, 200 V DC

Mechanical & Environmental

Parameter Specification
Net Weight 0.3 kg (0.7 lb)
Operating Temperature 0 to 60 degC (32 to 140 degF)
Storage Temperature -40 to 85 degC (-40 to 185 degF)
Relative Humidity 95% without condensation
Operating Altitude <= 5000 m (16404.2 ft)
Electrostatic Discharge Resistance 4 kV contact (IEC 801-2), 8 kV on air (IEC 801-2)
Electromagnetic Field Resistance 9.1 V/m (10 V/m) 80...1000 MHz (IEC 801-3)

Connections / Interfaces

Local Status Indicators

Indicator Color Function
Active LED Green Bus communication is present
External Fault LED Red External fault detected
Channel Status LEDs (8x) Green Individual channel turned on
Channel Fault LEDs (8x) Red Individual channel fault detected

Installation Guidelines

  1. Safety Precaution: Disconnect all system power and field transmitter wiring prior to mounting, wiring, or servicing the module to prevent electrical shock or equipment damage.
  2. Rack Insertion: Align the 140AVI03000 with the designated slot on the Modicon Quantum backplane rack. Firmly seats the module until the locking tabs snap into place.
  3. Wiring Connections: Wire field inputs to the appropriate terminal block following recommended polarity and channel assignments. Use shielded twisted-pair cabling for analog signal lines to minimize ambient noise.
  4. Shield Grounding: Connect cable shields to a single-point protective earth ground near the cabinet entry to prevent ground potential loops across isolated channels.
  5. Power Verification: Confirm backplane power availability matches the 280 mA bus current requirement before powering up the rack.

Configuration / Commissioning / Replacement

  • Software Setup: Configure module parameters within Unity Pro or Concept software, assigning the required 9 input words and specifying input ranges (current vs. voltage, unipolar vs. bipolar) per channel.
  • Loop Diagnostics Verification: Test fault detection features by checking broken wire responses on 4...20 mA channels and scale limit detection on 1...5 V spans.
  • Hot-Swapping / Replacement: Ensure system hot-swap procedures are followed if replacing the module under live rack power. Disconnect field terminal connectors, release backplane clips, insert the replacement 140AVI03000, and reattach the terminal block. Verify that the green Active LED turns on, indicating successful bus communications.

Compliance and Certifications

  • Standards: UL 508, CSA C22.2 No 142
  • Certifications: FM Class 1 Division 2, cUL, CE
  • Directives: EU RoHS Directive Compliant
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Schneider Electric 140AVI03000 Modicon Quantum Multirange Analog Input Module

What is the function of the Schneider Electric 140AVI03000 module?

The Schneider Electric 140AVI03000 is an 8-channel differential multirange analog input module designed for the Modicon Quantum automation platform. It processes bipolar and unipolar current and voltage signals from field sensors with 16-bit resolution for the PLC controller.

What input ranges are supported by the 140AVI03000?

The 140AVI03000 analog input module supports current ranges of 0...20 mA and bipolar 20 mA, as well as voltage ranges including 0...5 V, 0...10 V, +/- 5 V, and +/- 10 V.

Does the 140AVI03000 provide channel-to-channel isolation?

Yes, the Schneider Electric 140AVI03000 provides 135 Vrms AC / 200 V DC channel-to-channel isolation, as well as 500 Vrms AC / 750 V DC isolation between the channels and the Quantum backplane bus.

How many words does the 140AVI03000 require in the PLC addressing table?

The Schneider Electric 140AVI03000 requires 9 input words in the Quantum PLC controller memory addressing table for data transfer and diagnostic signaling.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Greyish White
Country of origin
France
Power source
DC Power

Recently Viewed Products

Technical knowledge

Implementing 3-Switch XOR Ladder Logic with Internal Bit

Implement a 3-SPST switch XOR light circuit in LogixPro or RSLogix 500 using an internal relay bit. Includes truth tables, boolean equations, and verified.

Building a Modbus RTU Network with CompactLogix and DeltaV

Integrate Allen-Bradley CompactLogix, Caterpillar ATS, and generators into DeltaV DCS over Modbus RTU. Covers ProSoft MVI69-MCM, Miille DIN266 gateways.

ONS Instruction Not Energizing OTE in Studio 5000 Ladder Logic

ONS instruction fires but the OTE coil never latches in Studio 5000 because the one-shot is only true for one scan. Use OTL/OTU or seal-in logic instead.

Kinetix 5500 EtherNet/IP Network Switch Requirements and Topology

Configure Allen-Bradley Kinetix 5500 servo drives on EtherNet/IP. Covers CIP Sync, IEEE 1588 V2 timing, Stratix selection, DLR topology, and HMI.

Moving Average Filtering in DCS and PLC Analog Control

A moving-average filter is the sliding-window smoother most instrument engineers drop into DCS and PLC analog paths. Here is how the window works, how N and sample time set lag, and when a...

GE Mark VI Function Blocks for Gas Turbine Control Logic

On Frame 5–9 gas turbines, GE Mark VI and Mark VIe run control as function-block application software. This article maps process, protection, and sequencing functions—and what Toolbox ST access...