The ABB PSTX840-600-70 (product ID 1SFA898119R7000 / 1SFA 8981 19 R7000) is a three-phase PSTX series softstarter engineered for controlled starting, stopping, and protection of medium- to large-sized three-phase AC induction motors. Operating across a main circuit voltage range of 208 to 600 V AC at 50/60 Hz with a 100 to 250 V AC control supply, the unit delivers a rated operational current of 840 A in an in-line connection (250 kW at 230 V, 450 kW at 400 V, and 600 kW at 500 V) or 1455 A in an inside-delta connection (450 kW at 230 V, 800 kW at 400 V, and 1000 kW at 500 V).
Equipped with three-phase voltage-ramp and torque-control algorithms, the PSTX840-600-70 integrates a built-in bypass contactor to minimize power losses during continuous running and simplify panel wiring. Operators interact via a detachable full-graphic display rated IP66 and UL Type 4X for outdoor panel mounting, while system integration is supported through hardwired Start/Stop/Reset inputs, three programmable digital inputs, four signaling relays, an analog output (0 to 10 V, 0 to 20 mA, or 4 to 20 mA), built-in Modbus RTU, and optional Anybus communication modules.
Features
Three-phase motor control supporting soft start and soft stop via voltage ramp or torque control
Built-in bypass for reduced heat dissipation, energy savings, and simplified cabinet installation
High current capacity rated at 840 A in-line and 1455 A inside-delta with a starting capacity of 4 x Ie for 10 seconds
Detachable full-graphic HMI display with IP66 and UL Type 4X outdoor environmental rating
Built-in electronic overload protection (EOL) with dual overload curves for start and run phases
Advanced motor control modes including kickstart, forward/reverse slow-speed jog, dynamic braking, standstill brake, pump cleaning, motor heating, sequence start, emergency/fire pump mode, and two-phase limp mode
Comprehensive electrical and thermal protection covering phase reversal, current/voltage imbalance, underload, locked rotor, ground fault, thyristor overload, and PTC/PT-100 temperature inputs
Built-in Modbus RTU communication plus support for optional Anybus modules (Profinet, Profibus, Modbus TCP, EtherNet/IP, EtherCAT, DeviceNet, CANopen, BACnet-IP, and BACnet-MSTP)
Four integrated status signaling relays (Run, By-pass/TOR, Fault, Overload) and configurable analog output (0 to 10 V, 0 to 20 mA, 4 to 20 mA)
Applications
Centrifugal and positive-displacement pumps, including municipal water systems and emergency/fire pump installations
Industrial ventilation fans, exhaust blowers, and HVAC air handling units
Rotary screw, reciprocating, and centrifugal air and gas compressors
Heavy-duty belt conveyors, crushers, and bulk material handling systems
High-inertia three-phase industrial machinery operating on 208 to 600 V AC mains
Detachable full-graphic display (IP66 and UL Type 4X outdoor rating)
Main Circuit Terminal Type
Busbars (Bars)
Tightening Torque (Main Circuit)
45 N-m (398.3 lb-in UL/CSA)
Connecting Capacity (Control & Supply Circuits)
Rigid 1 x 2.5 mm2
Degree of Protection
Main Terminals: IP00 (IEC 60529, IEC 60947-1, EN 60529); Graphic Display: IP66 / Type 4X
Ambient Operating Temperature
-25 to +60 degC
Ambient Storage Temperature
-40 to +70 degC
Dimensions (W x H x D)
435 mm x 493 mm x 369 mm
Net Weight
46.5 kg
Shipping Package Dimensions & Gross Weight
600 mm (W) x 616 mm (D) x 800 mm (H); 58.5 kg gross weight
Customs Tariff Number
85371091
Connections/Interfaces
Connector Pin
Function
Main Power Busbars
Three-phase line and motor load busbar connections rated up to 840 A in-line (1455 A inside-delta), tightened to 45 N-m
Control Supply Terminals (Us)
100 to 250 V AC (50/60 Hz) auxiliary control power input accepting rigid 1 x 2.5 mm2 conductors
Control Circuit & Digital Inputs (Uc)
24 V DC control circuit with hardwired Start, Stop, Fault Reset, and three programmable digital inputs (rigid 1 x 2.5 mm2)
Signal Output Relays
Normally Open (NO) relay outputs for Run, By-pass / Top of Ramp (TOR), Fault, and Overload status indication
Analog Output Terminals
Configurable analog feedback output supporting 0 to 10 V, 0 to 20 mA, or 4 to 20 mA signals
Temperature Sensor Inputs
Dedicated motor thermal protection inputs supporting PTC and PT-100 sensors
Built-in Fieldbus Interface
Integrated Modbus RTU serial communication interface and external Fieldbus plug adaptor support (PS-FBPA)
Anybus & HMI Expansion Ports
Front expansion slot for optional Anybus industrial Ethernet/fieldbus modules and port for the detachable IP66 graphic display or PSCA-1 USB cable
Installation Guidelines
Enclosure Protection: Because the main power terminals carry an IP00 protection rating, install the softstarter inside a suitable industrial control enclosure; optionally fit terminal shrouds (LT750-AC / LT750-AL) and terminal enlargements (LW750) or CuAl cable lug kits (1SDA013956R1 / 1SDA023380R1) for finger protection and conductor termination.
Busbar & Control Wiring Torque: Tighten main circuit busbar connections to 45 N-m (398.3 lb-in per UL/CSA specifications) and terminate control/supply wiring using rigid 1 x 2.5 mm2 conductors.
Connection Configuration: Select between standard in-line connection (up to 840 A) and inside-delta connection (up to 1455 A) using the integrated inside-delta configuration switch prior to commissioning.
Remote HMI Mounting: Detach the IP66 / Type 4X rated graphic display from the softstarter body and mount it on the cabinet door for external operator access and diagnostics without opening the enclosure.
Thermal Clearance & Operating Environment: Maintain ambient air temperatures within -25 to +60 degC inside the panel during operation.
Compliance and Certifications
CE: Compliant with European Union directives (Declaration of Conformity 2CMT005209)
UL / cULus: Rated for UL/CSA three-phase motor control up to 600 V AC and 800 Hp
CCC and CQC: Certified under China Compulsory Certification (2020980304001095 / 2020980304001491) and CQC (CQC2015010304830300 / CQC2015010304830295)
DNV: Marine and offshore type approval certificate TAE000087N
RoHS and REACH: Compliant with EU RoHS Directive 2011/65/EU and Amendment 2015/863 (2CMT2022-006500), EU REACH (2CMT2022-006481), and US TSCA (2CMT2023-006524)
Environmental & Data Compliance: ABB EcoSolutions validated with 81.9% recyclability per EN 45555, WEEE Category 5 B2B compliance, and EU Data Act compliance (1SFC132498M0201)
FAQ
What are the current and power ratings for the ABB PSTX840-600-70 softstarter?
The ABB PSTX840-600-70 (1SFA898119R7000) is rated for 840 A in an in-line connection (250 kW at 230 V, 450 kW at 400 V, 600 kW at 500 V) and up to 1455 A in an inside-delta connection (450 kW at 230 V, 800 kW at 400 V, 1000 kW at 500 V).
Does the PSTX840-600-70 include a built-in bypass and electronic overload protection?
Yes, the softstarter features an integrated bypass contactor to reduce running energy losses along with built-in dual electronic overload protection (EOL) for both start and run phases.
What communication protocols and control voltages are supported by 1SFA898119R7000?
It operates on a 100 to 250 V AC (50/60 Hz) control supply with a 24 V DC control circuit, includes built-in Modbus RTU, and supports Anybus modules for Profinet, Profibus, Modbus TCP, EtherNet/IP, EtherCAT, DeviceNet, CANopen, and BACnet.
Can the graphic display on the PSTX840-600-70 be mounted on a panel door?
Yes, the softstarter includes a detachable full-graphic display rated IP66 and UL Type 4X for outdoor and cabinet door mounting.
Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats Arabes Unis.
Retours et garantie
Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d'origine scellé en usine.
Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.
Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).
Pour connaître l'éligibilité complète, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel
Politique de remboursement et de retour
.
Une liste de contrôle technique pour remplacer un Allen-Bradley 1746-A7 : vérifiez la série du châssis, la charge du fond de panier, le plan des emplacements, les câbles d’interconnexion, le montage,...
Un guide de remplacement sur le terrain pour le GE Fanuc IC200MDL650, couvrant la logique négative selon la révision, quatre groupes courants, les seuils de 24 VCC, le filtrage des entrées, les...
Guide de remplacement de la carte IC697CPX935 axé sur le terrain, couvrant la mémoire rapide, le comportement du port série selon le micrologiciel, l’alimentation du rack, le refroidissement,...
Guide de remplacement du IC693DSM324 axé sur le terrain, couvrant les vérifications de l’unité hôte Series 90-30, les relevés de la chaîne d’asservissement FSSB, le budget d’alimentation 5 V, les...
Guide de remplacement HIMA F3430 axé sur le terrain, couvrant les caractéristiques nominales des contacts de relais, le déclassement des charges CC, les fusibles, les différences entre les F3330 et...
Un guide de remplacement de l’IC697PWR710 axé sur le terrain, couvrant le calcul de la charge à 5 V, les limites des configurations à deux racks, les câbles d’extension, les vérifications de...
Choisir une sélection entraîne un rafraîchissement complet de la page.