Integrating modular I/O systems directly with serial networks, the BK7300 Modbus RTU/ASCII Bus Coupler establishes a reliable interface between the Modbus fieldbus and decentralized Beckhoff Bus Terminals. This communication interface links up to 64 standard Bus Terminals to a central controller via an RS485 connection. It automatically detects connected terminal channels and structures them into the process image, enabling efficient handling of digital, analog, and specialized inputs and outputs.

The BK7300 coupler operates on Modbus RTU or Modbus ASCII protocols, which are configurable using rotary address switches or the proprietary KS2000 software tool. Designed for harsh industrial environments, this unit features a compact, DIN-rail mountable form factor and provides 500 V electrical isolation between the power contacts, the fieldbus interface, and the internal K-bus electronics.

Features

  • Direct integration of up to 64 standard Beckhoff Bus Terminals.
  • Supports both Modbus RTU and Modbus ASCII protocols (RTU default setting).
  • Flexible node addressing via hardware rotary switches or software configuration.
  • Generous process image capacity supporting up to 512 bytes of input and 512 bytes of output data.
  • Robust RS485 serial interface housed in a standard D-sub 9-pin connection.
  • Integrated K-bus power supply providing up to 1750 mA current output for terminal electronics.

Applications

  • Decentralized process automation and plant control.
  • Factory automation and production assembly lines.
  • Building automation, HVAC, and utility monitoring networks.
  • Industrial machinery control with modular diagnostic demands.

Technical Specifications

Manufacturer Beckhoff Automation
Part Number / Model BK7300
Product Type Modbus Bus Coupler
Protocol Modbus RTU / Modbus ASCII (default: RTU)
Bus Interface D-sub 9-pin (RS485)
Number of Bus Terminals 64 (up to 255 with K-bus extension)
Max. Process Image Size 512 bytes input / 512 bytes output
Digital Peripheral Signals 512 inputs/outputs
Analog Peripheral Signals 256 inputs/outputs
Configuration Interface Rotary switch or KS2000 configuration software
Power Supply Voltage 24 V DC (-15% / +20%)
Input Current 70 mA + (total K-bus current)/4 (max. 500 mA)
Starting Current 2.5 x continuous current
Recommended Fuse Protection Less than or equal to 10 A
Current Supply K-Bus 1750 mA
Power Contacts Voltage 24 V DC max.
Power Contacts Current 10 A max.
Electrical Isolation 500 V (power contacts / supply voltage / fieldbus)
Weight Approx. 170 g
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95%, non-condensing
Vibration Resistance Conforms to EN 60068-2-6
Shock Resistance Conforms to EN 60068-2-27
EMC Immunity / Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Protection Class IP20

Connections and Interfaces

D-sub 9-Pin Pinout Signal Assignment (RS485)
Pin 1 Shield (Screen)
Pin 3 RxD/TxD-B (Positive Data Line)
Pin 5 GND (Signal Ground)
Pin 6 VP (+5 V supply for active termination)
Pin 8 RxD/TxD-A (Negative Data Line)

Installation Guidelines

  • Mount the coupler horizontally on standard 35 mm DIN rails conforming to EN 60715.
  • Ensure an adequate ventilation gap above and below the module to allow convection cooling.
  • Ensure the system power is completely disconnected before inserting or removing any Bus Terminals or changing wiring.
  • Connect the PE (Protective Earth) contact directly to the DIN rail to maintain low-impedance grounding.
  • Ensure active RS485 termination resistors are installed at both physical ends of the Modbus segment.

Compliance and Certifications

  • CE
  • UL (cULus)
  • Explosion Protection (Ex)
  • Germanischer Lloyd (GL)
Loading product navigation…

What communication protocols does the BK7300 support?

The BK7300 supports Modbus RTU and Modbus ASCII. Modbus RTU is configured as the default setting.

How do you set the station address on the BK7300?

The station address and network configuration can be set manually via the integrated rotary address switches on the unit or digitally via the KS2000 configuration software.

What is the maximum K-bus current supply of the BK7300?

The BK7300 has a maximum K-bus current supply capacity of 1750 mA (1.75 A) for the downstream terminal modules.

What type of connection interface is used for the fieldbus on this module?

The fieldbus interface uses a standard 9-pin female D-sub connector utilizing an RS485 serial connection.

How many Bus Terminals can be connected to a single BK7300 coupler?

Up to 64 standard Bus Terminals can be connected directly. This number can be expanded up to 255 using K-bus extension terminals.

Expédition express mondiale

  • Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
  • Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
  • Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats arabes unis.

Retours et garantie

  • Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d'origine scellé en usine.
  • Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.

Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).


Pour connaître l'éligibilité complète, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel Politique de remboursement et de retour .

TECHNICAL SPECIFICATIONS

Country of origin
Allemagne

Produits récemment consultés

Connaissances techniques

Actionneurs électriques conçus pour remplacer les systèmes à fluide : un guide pratique d'automatisation industrielle

Cet article explique comment les actionneurs électriques intégrés, tels que la série e-Actuator de SMC, transforment le contrôle du mouvement industriel en remplaçant les systèmes pneumatiques et...

Opérations mathématiques avec OpenPLC pour les applications d'automatisation industrielle

Cet article explique comment les systèmes PLC réalisent des opérations mathématiques de base telles que l'addition, la soustraction, la multiplication, la division, le modulo et l'exponentiation dans...

Logique booléenne avancée avec la programmation FBD PLC : applications industrielles pratiques au-delà de la logique de base

L'article explique plusieurs fonctions avancées de la logique booléenne utilisées en programmation d'automates programmables industriels (API) au-delà des opérations de base ET, OU et NON. Il aborde...

Logique booléenne en programmation PLC : comprendre les portes logiques FBD

La logique booléenne est la base de tout programme PLC. Des commandes machines simples aux systèmes d'automatisation industrielle complexes, les portes logiques déterminent comment les contrôleurs...

Guide approfondi sur les pare-feux industriels et la segmentation des réseaux OT

Les pare-feux industriels jouent un rôle crucial dans la cybersécurité OT, protégeant les réseaux PLC, DCS et SCADA grâce à la segmentation, au contrôle des entrées/sorties et à l’intégration IDS/IPS...

Guide des pinces robotiques : de la manipulation délicate à l'automatisation lourde

Les pinces robotiques modernes évoluent au-delà des mâchoires mécaniques traditionnelles. Des systèmes adhésifs inspirés des geckos aux pinces souples de qualité alimentaire, en passant par des...