1 de 1

FX5-32ET/ES | Mitsubishi Electric | Module E/S alimenté (AC)

FX5-32ET/ES | Mitsubishi Electric | Module E/S alimenté (AC)

Il ne reste que 10 article(s) en stock
  • Fabricant : Mitsubishi Electric

  • N° de produit : FX5-32ET/ES

  • Pays d'origine :États-Unis

  • Type de produit : Module E/S alimenté (AC)

  • Paiement : Virement bancaire, Western Union

  • Poids : 650g

  • Dimensions : 150 mm x 90 mm x 83 mm

  • Port d'expédition : Xiamen

  • Garantie : 12 mois

Quantité
Voir les détails complets

Description

Designed to expand the local control capacity of MELSEC iQ-F series programmable controllers, the FX5-32ET/ES extension block provides integrated power supply capabilities alongside high-density digital I/O interfaces. This powered extension module features a built-in AC power supply, which significantly reduces the current draw on the host CPU module's internal 5V DC and 24V DC buses, enabling complex system expansion without requiring additional power booster units.

The unit occupies 32 I/O points on the active PLC backplane, split evenly between inputs and outputs. The input stage contains 16 points configurable for either sink or source wiring configurations, while the output stage consists of 16 low-latency transistor outputs in a sink configuration, making it suitable for high-speed switching and interfacing with solid-state control components.

Features

  • Equipped with an onboard 100 to 240 V AC power supply to power downstream extension modules and field devices.
  • Provides 32 local digital I/O points (16 digital inputs and 16 transistor outputs) in a single compact enclosure.
  • Flexible digital inputs compatible with both 24 V DC sink and source signal wiring.
  • Reliable transistor outputs (sink type) designed for rapid duty cycles and maintenance-free solid-state switching.
  • Removable terminal blocks simplify installation, wiring, and routine system maintenance.
  • Direct connection to the FX5U CPU module or preceding expansion blocks via the integrated extension cable.

Applications

  • Automated assembly lines and material handling conveyor systems.
  • Packaging, wrapping, and labeling machinery.
  • Water and wastewater treatment control panels.
  • HVAC and environmental control cabinets.
  • Multi-axis motion control and positioning system expansions.

Technical Specifications

ManufacturerPart Number / ModelSeriesModule TypeOccupied I/O PointsPower Supply VoltageAllowable Voltage RangePower ConsumptionService Power SupplyInput PointsOutput PointsResponse Time (Inputs)Response Time (Outputs)Operating Ambient TemperatureStorage Ambient TemperatureDimensions (W x H x D)Weight
Mitsubishi Electric
FX5-32ET/ES
MELSEC iQ-F Series
Powered I/O Module (AC powered)
32 points (on PLC bus)
100 to 240 V AC (50/60 Hz)
85 to 264 V AC
25 W
24 V DC (310 mA maximum capacity)
16 points (24 V DC, sink/source configuration)
16 points (Transistor, sink configuration)
50 microseconds or less (OFF to ON / ON to OFF)
0.2 milliseconds or less
0 to 55 degC
-25 to 75 degC
150 mm x 90 mm x 83 mm
0.65 kg

Connections and Interfaces

Terminal Group Terminal Markings Function / Connection Description
Power Supply Terminals L, N, PE 100 to 240 V AC Power Line and Protective Earth Ground
Service Power Output 24+, 24- 24 V DC auxiliary power output for sensors/input devices
Digital Inputs (16 Points) S/S, X0 to X17 Sink/Source common terminal and digital inputs
Digital Outputs (16 Points) COM0, COM1, Y0 to Y17 Common terminals and transistor (sink) outputs

Installation Guidelines

  • Mounting: Mount the module on a standard 35 mm DIN rail or secure directly to a flat panel using the integrated mounting screw holes.
  • Spacing: Maintain a minimum clearance of 50 mm above and below the unit to promote natural convection cooling and prevent thermal stress.
  • Grounding: Connect the Protective Earth (PE) terminal to a dedicated ground point using a wire with a minimum cross-section of 2 mm squared. Ground resistance must be 100 Ohms or less.
  • Wiring: Use crimp terminals designed for M3 terminal screws. Tighten terminal screws to a torque spec of 0.5 to 0.8 N-m to prevent contact resistance or damage.

What is the primary function of the FX5-32ET/ES powered I/O module?

The FX5-32ET/ES expands the physical I/O capacity of a MELSEC iQ-F PLC system by 32 channels. Because it has an onboard AC power supply, it powers its own I/O channels and can supply auxiliary power to sensors, reducing the power load on the main CPU module.

Are the input terminals on the FX5-32ET/ES configurable for both NPN and PNP devices?

Yes. The 16 digital inputs feature a sink/source common terminal (S/S), allowing you to configure the module for either sink (NPN) or source (PNP) wiring.

What output type is used in the FX5-32ET/ES module?

This module is equipped with 16 transistor outputs in a sink configuration, making them suitable for high-speed, high-cycle switching of DC loads.

Can I use the auxiliary 24V DC terminal on this module to power external field devices?

Yes, the module provides a 24V DC service power output terminal with a maximum capacity of 310 mA to power local sensors and input switches.

Expédition express mondiale

  • Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
  • Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
  • Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats arabes unis.

Retours et garantie

  • Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d’origine scellé en usine.
  • Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.

Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).


Pour connaître les conditions d’éligibilité complètes, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel Politique de remboursement et de retour .

TECHNICAL SPECIFICATIONS

Country of origin
États-Unis

Produits récemment consultés

Connaissances techniques

Logique booléenne avancée avec la programmation FBD PLC : applications industrielles pratiques au-delà de la logique de base

L'article explique plusieurs fonctions avancées de logique booléenne utilisées en programmation d'automates programmables industriels (API) au-delà des opérations de base ET, OU et NON. Il aborde...

Logique booléenne en programmation PLC : comprendre les portes logiques FBD

La logique booléenne est la base de tout programme PLC. Des commandes machines simples aux systèmes d'automatisation industrielle complexes, les portes logiques déterminent comment les contrôleurs...

Guide approfondi sur les pare-feux industriels et la segmentation des réseaux OT

Les pare-feux industriels jouent un rôle crucial dans la cybersécurité OT, protégeant les réseaux PLC, DCS et SCADA grâce à la segmentation, au contrôle des entrées/sorties et à l'intégration IDS/IPS...

Guide des préhenseurs robotiques : de la manipulation délicate à l'automatisation lourde

Les pinces robotiques modernes évoluent au-delà des mâchoires mécaniques traditionnelles. Des systèmes adhésifs inspirés du gecko et des pinces souples de qualité alimentaire aux outils d'entrepôt...

Retour en arrière : comment les premiers moteurs électriques ont transformé l'exploitation minière souterraine

Des compresseurs à courant continu entraînés par corde aux wagonnets de mine alimentés par batterie, les premières opérations minières ont marqué un tournant dans l’électrification industrielle. Cet...

Factory I/O : un outil moderne de simulation PLC pour la formation à l'automatisation industrielle

Factory I/O révolutionne l'enseignement des automates programmables industriels (API) en proposant des simulations industrielles 3D immersives pour les étudiants, les ingénieurs et les équipes de...