Honeywell

Honeywell CC-TDOB01 Series C 24V Digital Output IOTA 9-Inch Non-Redundant

SKU CC-TDOB01

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Honeywell

  • Product No.: CC-TDOB01

  • Country of origin:United States

  • Product Type: Digital Output IOTA Board

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 450g

  • Dimensions: 228.6 x 127.0 x 40.0 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The Honeywell CC-TDOB01 is a 9-inch non-redundant Digital Output 24V Input Output Termination Assembly (IOTA) designed for the Honeywell Experion PKS Series C architecture. It serves as the physical interface layer connecting field-level actuators, relays, indicators, and solenoids to the corresponding Series C Digital Output 24V I/O Module (IOM).

Engineered to support up to 32 discrete channels, the assembly routes control signals and power directly to field devices through dedicated terminal block connections. The architecture supports field wiring protection mechanisms integrated with the IOM, including individual channel current monitoring and over-current shutdown features.

The board accommodates flexible system powering options, accepting both internal system power or customer-supplied external 24V DC power sources. Its non-redundant 9-inch footprint offers a compact installation footprint for standardized control cabinets in industrial automation environments.

Features

  • 32-Channel Field Termination: Provides dedicated power and return screw connections for 32 discrete 24V DC output channels across two primary terminal blocks.
  • Selective Over-Current Protection Support: Works with the digital output module to sense field shorts, automatically shutting down only the affected point while leaving non-faulted channels operational.
  • Soft Failure Diagnostic Signaling: Facilitates an Over-current Soft Failure alarm generation and switches the faulted point mode to Manual until the short circuit is resolved.
  • Thermal Protection Monitoring: Supports thermal protection alarming for field short circuit conditions exceeding 0.5A.
  • Flexible Power Source Configuration: Configurable via Terminal Block 3 to select between Honeywell internal 24V power supply or external customer-supplied 24V power.
  • Compact Non-Redundant Footprint: Standardized 9-inch Series C board profile designed for efficient cabinet space utilization.

Applications

  • Process Output Actuation: Interfacing Experion PKS Series C controllers with field solenoids, interposing relays, and control valves.
  • Industrial Plant Annunciation: Driving discrete field indicators, alarms, stack lights, and status panels.
  • Discrete System Control: Providing 24V DC switching logic for batch, continuous process, and manufacturing automation infrastructure.

Technical Specifications

Parameter Specification
Manufacturer Honeywell
Model CC-TDOB01
Product Type Digital Output 24V IOTA
System Platform Experion PKS Series C
Configuration Non-Redundant
Size Profile 9-Inch
Channel Capacity 32 Channels
Field Power Supply Voltage 24V DC
Power Source Options Internal System Power / External Customer Power
Short Circuit Protection Threshold > 0.5A (Thermal Protection Alarm)
Fault Reaction Individual channel shutdown; Mode set to Manual
Terminal Blocks TB1 (Channels 1-16), TB2 (Channels 17-32), TB3 (Power Selection)

Connections / Interfaces

Interface / Terminal Block Pin / Screw Function
TB1 (Channels 1–16) Odd Screws (1, 3, ... 31) Channel Power Screws (Ch 1 to Ch 16)
  Even Screws (2, 4, ... 32) Channel Return Screws (Ch 1 to Ch 16)
TB2 (Channels 17–32) Odd Screws (1, 3, ... 31) Channel Power Screws (Ch 17 to Ch 32)
  Even Screws (2, 4, ... 32) Channel Return Screws (Ch 17 to Ch 32)
TB3 (Power Input) Screw 1 Internal 24V
  Screw 2 Internal Return
  Screw 3 External 24V
  Screw 4 External Return

Installation Guidelines

  1. Inspect the IOTA board for mechanical integrity prior to installation in the Series C cabinet.
  2. Mount the 9-inch IOTA board onto the panel rack or enclosure backplate following Series C spacing standards.
  3. Confirm whether internal or external 24V power will be utilized and wire Terminal Block 3 accordingly.
  4. Ensure proper power polarity on external supply lines to prevent module damage.
  5. Wire field devices to Terminal Blocks 1 and 2, securing positive leads to power screws and negative leads to return screws.
  6. Seat the corresponding Series C 24V Digital Output IOM firmly into the card position on the IOTA assembly.

Replacement Recommendations

  1. Verify that the replacement part number matches CC-TDOB01.
  2. Disconnect field power supplying Terminal Block 3 if using an external power source.
  3. Remove the associated I/O Module from the IOTA card connector.
  4. Label and disconnect field wiring screw terminal plugs or leads from TB1, TB2, and TB3.
  5. Unmount the degraded IOTA board, mount the new assembly, reconnect wiring plugs, and reinsert the IOM.
  6. Reapply power and verify channel diagnostic status in Experion PKS system software.

FAQ

What is the primary function of the Honeywell CC-TDOB01?

The Honeywell CC-TDOB01 is a 9-inch non-redundant Input Output Termination Assembly (IOTA) designed to connect 32 field-level 24V DC discrete output devices directly to a Honeywell Experion PKS Series C Digital Output Module.

How does the Honeywell CC-TDOB01 handle field short circuits?

When a short circuit occurs on a connected channel, the output circuit senses the over-current condition, trips a thermal alarm if above 0.5A, shuts down only the affected point, switches that point's mode to Manual, and triggers an Over-current Soft Failure alarm without interrupting other channels.

Can the Honeywell CC-TDOB01 use an external 24V power supply?

Yes, Terminal Block 3 on the assembly allows selection between an internal Honeywell power supply and a customer-supplied external 24V power source. External power wiring must maintain correct polarity to prevent damage.

How many channels does the Honeywell CC-TDOB01 IOTA support?

The Honeywell CC-TDOB01 termination assembly supports up to 32 individual 24V DC digital output channels distributed across Terminal Block 1 (Channels 1–16) and Terminal Block 2 (Channels 17–32).

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell CC-TDOB01 Series C 24V Digital Output IOTA 9-Inch Non-Redundant

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 3
Only 5 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Greyish White
Country of origin
United States
Power source
DC Power

Technical knowledge

1756-OF4 Output Wrong? Check Mode, RTB, and Scaling First

A field-first diagnostic sequence for 1756-OF4 analog output problems: channel mode, removable terminal block, scaling, and controlled electrical checks.

1746-OA8 vs 1746-OA16: Output Count and Current Limits

A direct comparison of 1746-OA8 and 1746-OA16 output count, common grouping, backplane current and temperature-derated load limits.

Replacing a 1761-NET-DNI: Capture These Settings First

A field checklist for recording the 1761-NET-DNI hardware series, firmware, EDS file, DF1 settings, DeviceNet address and messaging configuration before replacement.

EL3062 vs EL3062-0030: The Input Range Changes

The EL3062 is a 0–10 V EtherCAT terminal. The EL3062-0030 is a 0–30 V variant. This checklist covers identification, scaling and commissioning.

Replacing a 1769-OW8: Checks Before Moving Relay Loads

A field checklist for replacing Allen-Bradley 1769-OW8 relay output modules without losing load-group, wiring, and commissioning details.

PLC I/O Modules: Wiring, Load, and Isolation Checks

A field checklist for matching PLC digital and analog I/O to sensors, loads, commons, isolation groups, filters, and replacement settings.