Description
Actuating as a dedicated integration link, the Beckhoff KS6771 Bus Terminal enables direct, bidirectional communication between a K-bus coupler and Belimo MP-Bus HVAC field devices. This module functions as an MP-Bus master, coordinating data acquisition and control command distribution over a single channel. The KS6771 design features a pluggable wiring level, allowing swift module swaps without disconnecting field-level wiring harnesses. Integration is fully managed via standard TwinCAT PLC function blocks, streamlining commissioning across complex commercial and industrial air handling architectures.
Features
-
Multi-Device Topologies: Controls up to 16 MP-Bus devices (maximum 8 drives and 8 sensors) over a single fieldbus drop.
-
Pluggable Wiring Interface: Uses tension-clamp connection terminals that can be detached as a single block for expedited terminal replacement.
-
Galvanic Isolation: Provides robust 500 V isolation between the internal K-bus and the external MP-Bus circuitry to suppress common-mode electrical noise.
-
Efficient Process Image: Maps directly into the controller configuration utilizing 12 bytes of input data and 12 bytes of output data.
-
Standardized Diagnostics: Fully compatible with the TwinCAT PLC MP-Bus software library for fast system integration and continuous error reporting.
Applications
-
HVAC Variable Air Volume (VAV) Systems: Direct control of volumetric flow controllers, damper actuators, and temperature sensors.
-
Industrial Environmental Controls: Closed-loop control of pressure relief valves and air-handling units within cleanrooms or pharmaceutical laboratories.
-
Building Management Systems (BMS): Integration of distributed Belimo valve actuators and auxiliary sensors into high-level Ethernet/IP or EtherCAT backbones.
Technical Specifications
| Parameter |
Specification |
| Manufacturer |
Beckhoff Automation |
| Model Number |
KS6771 |
| Interface Type |
MP-Bus Master (1 Channel) |
| Data Transfer Rate |
1200 baud |
| Bus Access Protocol |
Polling |
| Nominal System Voltage |
24 V DC (-15% / +20%) |
| K-Bus Current Consumption |
Typically 55 mA |
| Power Contact Consumption |
Typically 10 mA + actuator load |
| Maximum Power Contact Load |
10 A |
| Isolation Voltage |
500 V (K-bus to MP-Bus line) |
| Process Image Width |
12 bytes input, 12 bytes output |
| Connection Cross-Section |
0.08 to 1.5 mm² (AWG 28...16 solid/stranded; AWG 26...16 flexible) |
| Wire Stripping Length |
9 to 10 mm |
| Environmental Rating |
IP20 (with variable installation orientation) |
| Operating Temperature |
0 to +55 degC |
| Storage Temperature |
-25 to +85 degC |
| Relative Humidity |
95% non-condensing |
| Vibration/Shock Resistance |
Conforms to EN 60068-2-6 / EN 60068-2-27 |
| EMC Immunity/Emission |
Conforms to EN 61000-6-2 / EN 61000-6-4 |
| Explosion Protection Marking |
II 3 G Ex nA IIC T4 Gc (ATEX Zone 2) |
| Housing Material |
Polycarbonate (terminal housing with pluggable wiring) |
| Dimensions (W x H x D) |
12 mm x 100 mm x 68 mm |
| Product Net Weight |
Approximately 85 g |
| Shipping Weight (Calculated) |
1.5 kg |
Connections and Interfaces
| Terminal Pin Number |
Signal Assignment |
Description |
| 1 |
MP-Bus Line |
Bidirectional communications line to Belimo slave actuators. |
| 2 |
24 V DC (Power Contact) |
Power feed to drive units (internally bridged to power contact). |
| 5 |
GND (MP-Bus Reference) |
Common reference potential for MP-Bus communication. |
| 6 |
0 V DC (Power Contact) |
Negative power rail reference (internally bridged to power contact). |
Empirical Engineering Insights
Alternative Models & Compatibility
The KS6771 is direct operational equivalent to the standard KL6771 Bus Terminal. The critical difference lies in the "KS" terminal housing design, which includes a pluggable wiring block. From a software perspective, the TwinCAT hardware configuration treats the KS6771 identically to the KL6771, enabling seamless drop-in replacements in existing PLC programs without necessitating code modifications or IO mapping updates.
Application Pitfalls & Engineering Notes
When deploying the KS6771, engineers must monitor total current consumption on the external 24 V DC supply loop. The terminal relies on internal power contacts rated for a maximum of 10 A. If several heavy damper drives are powered directly through the bus terminal, ensure the combined peak inrush currents do not exceed this threshold. For installations spanning long physical distances, use shielded twisted-pair cables to mitigate inductive noise coupling, which can disrupt the 1200-baud polling cycles.
Commissioning & Wiring Tips
To configure the bus terminal within the TwinCAT environment, the Tc2_MPBus library must be integrated into the PLC project. When addressing Belimo devices, remember that the MP-Bus allows 8 active control drives and 8 passive sensors. When inserting stranded field conductors, use the pluggable tension-clamp release slot with a standard flat-head screwdriver (3.0 mm blade size) to avoid damaging the polycarbonate terminal guide locks.
Installation Guidelines
CRITICAL WARNING: Prior to installing, removing, or wiring the KS6771 terminal, completely de-energize the main system controller and all auxiliary 24 V power feeds. Failure to isolate power may cause communication bus disruption or permanent damage to the solid-state K-bus interface electronics.
1
Mount the terminal on a standard 35 mm DIN rail conforming to EN 60715, ensuring the lock mechanism snaps firmly into place.
2
Slide adjacent terminals together, using the integrated double slot and key connection for side-by-side electrical contact.
3
Prepare field wires by stripping insulation precisely to 9–10 mm, avoiding loose strands that could cross-contact neighboring terminals.
4
Insert field wiring into the pluggable tension clamps, using a spring-release screwdriver tool to lock each wire securely into position.