Engineered for precise speed and torque control in three-phase industrial environments, the Mitsubishi Electric FR-E840-0120-4-60 serves as a highly reliable 400V class variable frequency drive within the FR-E800 series portfolio. This compact inverter is rated for a Normal Duty (ND) current of 12.0 A, delivering robust performance under heavy cyclic loads. Designed to thrive in demanding automation settings, this unit includes standard conformally coated circuit boards to guard against atmospheric contaminants and moisture, making it an excellent match for material handling, HVAC, and pumping operations. Utilizing Source logic for its control and safety stop inputs, it integrates smoothly into standard safety-instrumented systems requiring high uptime and predictable safety response.

Key Features

  • Conformal Circuit Board Coating: Enhanced environmental protection (-60 designation) prevents corrosion and tracking faults from dust and humidity.
  • Source Logic System: Built-in Source logic for standard digital inputs and fixed Source logic for integrated safety stop signals.
  • AM Terminal Voltage Monitoring: Outfitted with an analog voltage monitoring output (Terminal AM) for real-time operation tracking.
  • Advanced Thermal Management: Compact design with built-in cooling fan optimized for tight control panel spacing.
  • Integrated Safety Stop: Supports functional safety requirements with dedicated dual-channel safety inputs to isolate motor power safely.

Industrial Applications

  • Conveyor and Logistics Systems: Smooth acceleration and deceleration control for heavy-load conveyor lines.
  • Pumping and Fan Systems: Energy-efficient variable flow and pressure regulation using built-in PID control loops.
  • Packaging Machinery: High-response speed profiles matching operational packaging sequences.
  • Textile and Material Processing: Constant tension and winding controls utilizing precise analog monitoring feedback.

Technical Specifications

Parameter Specification Value
Manufacturer Mitsubishi Electric
Model Number FR-E840-0120-4-60
Series Name FR-E800 (FR-E8)
Voltage Class 400 V Class (Three-Phase Input)
Inverter ND Rated Current 12.0 A
Rated Frequency (Initial Setting) 50 Hz
Input Signal (Initial Status) Source logic
Safety Stop Signal Logic Source logic (Fixed)
Monitoring Interface Voltage (Terminal AM)
Circuit Board Coating Conformally coated boards (with coating)
Plated Conductor Without plated conductors
Cooling Type Forced Air Cooling
Net Weight 2.4 kg
Shipping Weight (Calculated) 5.0 kg

Connections and Interfaces

Terminal Symbol Terminal Name Description / Signal Allocation
R/L1, S/L2, T/L3 Main Circuit Power Input Connects to the three-phase AC power supply (380 to 480 V AC, 50 Hz / 60 Hz).
U, V, W Inverter Output Terminals Connects to the three-phase induction or permanent magnet motor.
AM Analog Monitor Output Provides analog voltage output (0 to 10 VDC) for monitoring parameter values.
PC External Transistor Common Acts as the 24 VDC common power supply source for digital inputs (Source logic configuration).
S1, S2, SIC Safety Input Terminals Used for functional safety shutdown loops (STO) in compliance with SIL2/SIL3 standards.

Empirical Engineering Insights

Alternative Models & Compatibility

When migrating legacy systems from the older FR-E740-120-EC or FR-E740-120-NA, the newer FR-E840-0120-4-60 offers matching physical mounting dimensions but incorporates advanced safety logic and enhanced parameter groups. Be sure to backup your original parameters via FR Configurator2 software. When downloading to the FR-E840, some advanced motor constants may need manual conversion if operating older non-standard permanent magnet motors.

Application Pitfalls & Engineering Notes

Operating this inverter inside tightly enclosed, sealed panels can result in localized thermal build-ups. Ensure that surrounding clearance parameters (minimum 50 mm above and below, 20 mm on the sides) are strictly maintained to permit effective convection. When wiring safety inputs (S1 and S2), note that the safety stop terminal logic is fixed to Source logic. Attempting to use a 0V common path to control safety circuits on this specific model variant will cause hard safety interlock faults (e.g., SA status fault indication).

Commissioning & Wiring Tips

To minimize high-frequency electromagnetic interference (EMI) on the analog AM monitoring terminal, always utilize a separate shielded twisted pair (STP) cable for control signals. Ground the shield at the inverter side only, specifically to the dedicated control ground terminal. If the motor cables exceed 30 meters in length, install an output dV/dt filter or reduce the carrier frequency (Pr. 72) to prevent excessive leakage currents and premature insulation aging in the motor windings.

Installation Guidelines

CRITICAL ELECTRICAL SAFETY WARNING Ensure the input main power line (R/L1, S/L2, T/L3) is completely de-energized and locked out before initiating any wiring or terminal access. The intermediate DC link capacitors retain dangerous electrical potential after power-off. Wait a minimum of 10 minutes following complete power disconnection, and verify that the charge indicator LED on the face of the unit is completely off before servicing terminal connections.
1 Securely mount the inverter vertically on a flat, vibration-free surface. Ensure that airflow to the heatsink fins is not obstructed by conduit runs or wire trays.
2 Route the main power lines separately from the low-voltage control lines (safety, analog output, and logic circuits) to prevent signal coupling and electromagnetic cross-talk.
3 Ensure the grounding terminal (PE) is bonded to the main system ground bus via a heavy-gauge, low-impedance conductor (minimum cross-section equivalent to power conductors).
4 Perform a continuity check on all output phases (U, V, W) to confirm that no phase-to-phase or phase-to-ground short circuits exist before powering up the drive.

What does the -60 suffix indicate on this specific drive?

The -60 suffix specifies that the control circuit boards have a conformal coating for enhanced environmental protection against humidity and conductive dust, but without nickel/tin-plated copper conductors.

What is the rated current for this model in Normal Duty?

The rated output current is 12.0 Amps under Normal Duty (ND) conditions at 400V class three-phase input.

Can the control logic be configured for Sink logic instead of Source logic?

No, the safety stop signal logic is fixed to Source logic for this specific model configuration (-4 variant).

What parameter controls the initial frequency setting on this unit?

The initial base frequency setting is pre-programmed to 50 Hz, but can be modified via Parameter 3 (Base Frequency) to match 60 Hz networks during initial setup.

Expédition express mondiale

  • Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
  • Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
  • Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats arabes unis.

Retours et garantie

  • Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d'origine scellé en usine.
  • Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.

Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).


Pour connaître l'éligibilité complète, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel Politique de remboursement et de retour .

TECHNICAL SPECIFICATIONS

Country of origin
États-Unis

Produits récemment consultés

Connaissances techniques

Actionneurs électriques conçus pour remplacer les systèmes à fluide : un guide pratique d'automatisation industrielle

Cet article explique comment les actionneurs électriques intégrés, tels que la série e-Actuator de SMC, transforment le contrôle du mouvement industriel en remplaçant les systèmes pneumatiques et...

Opérations mathématiques avec OpenPLC pour les applications d'automatisation industrielle

Cet article explique comment les systèmes PLC réalisent des opérations mathématiques de base telles que l'addition, la soustraction, la multiplication, la division, le modulo et l'exponentiation dans...

Logique booléenne avancée avec la programmation FBD PLC : applications industrielles pratiques au-delà de la logique de base

L'article explique plusieurs fonctions avancées de la logique booléenne utilisées en programmation d'automates programmables industriels (API) au-delà des opérations de base ET, OU et NON. Il aborde...

Logique booléenne en programmation PLC : comprendre les portes logiques FBD

La logique booléenne est la base de tout programme PLC. Des commandes machines simples aux systèmes d'automatisation industrielle complexes, les portes logiques déterminent comment les contrôleurs...

Guide approfondi sur les pare-feux industriels et la segmentation des réseaux OT

Les pare-feux industriels jouent un rôle crucial dans la cybersécurité OT, protégeant les réseaux PLC, DCS et SCADA grâce à la segmentation, au contrôle des entrées/sorties et à l’intégration IDS/IPS...

Guide des pinces robotiques : de la manipulation délicate à l'automatisation lourde

Les pinces robotiques modernes évoluent au-delà des mâchoires mécaniques traditionnelles. Des systèmes adhésifs inspirés des geckos aux pinces souples de qualité alimentaire, en passant par des...