1 of 1

FR-A840-1.5K-1 | MITSUBISHI | Variateur de Vitesse/Fréquence (VSD/VFD) / Onduleur

FR-A840-1.5K-1 | MITSUBISHI | Variateur de Vitesse/Fréquence (VSD/VFD) / Onduleur

Il ne reste que 10 article(s) en stock
  • Fabricant : Mitsubishi Electric

  • N° de produit : FR-A840-1.5K-1

  • Pays d'origine :États-Unis

  • Type de produit : Variateur de vitesse/fréquence (VSD/VFD) / Onduleur

  • Paiement : Virement bancaire, Western Union

  • Poids : 4500g

  • Dimensions : 260 mm x 150 mm x 140 mm

  • Port d'expédition : Xiamen

  • Garantie : 12 mois

Quantité
Voir les détails complets

Description

Designed for high-performance industrial motor control, the FR-A840-1.5K-1 by Mitsubishi Electric operates as a premium variable frequency drive within the FR-A800 series. This high-capacity inverter delivers exceptional speed and torque control for 1.5 kW three-phase motors, relying on advanced real-time sensorless vector control algorithms. Built to withstand demanding manufacturing environments, the unit integrates standard serial communication architectures, high-efficiency cooling, and robust overcurrent protection to ensure continuous field operation and minimize plant downtime.

Features

  • Real-time sensorless vector control capabilities for ultra-precise speed and torque response.
  • Built-in RS-485, RS-422, and RS-232 serial communication interfaces supporting Modbus RTU protocols.
  • Dual overload rating tolerance designed for versatile normal duty (ND) and light duty (LD) load characteristics.
  • Embedded safety-related stop function conforming to international industrial standards.
  • Integrated EMC filter to minimize electromagnetic noise and safeguard adjacent control instrumentation.

Applications

  • Material handling conveyor lines requiring precise acceleration and deceleration profiles.
  • Centrifugal pump systems and industrial fan setups utilizing variable torque optimization.
  • Extrusion lines and continuous mixers within chemical and plastics processing facilities.
  • Machine tool spindles requiring stable speed holding under variable mechanical loads.

Technical Specifications

Parameter Value
Manufacturer Mitsubishi Electric
Model Reference FR-A840-1.5K-1
Series Name FR-A800
Input Voltage Class Three-phase 400 V (380 to 500 VAC, 50/60 Hz)
Applicable Motor Capacity 1.5 kW
Output Rated Current 4.0 A
Output Rated Capacity 3.0 kVA
Communication Interfaces RS-232, RS-422, RS-485 (Mitsubishi / Modbus RTU)
Standards & Approvals CE, UL, cUL, RoHS
Enclosure Rating IP20
Physical Dimensions (H x W x D) 260 mm x 150 mm x 140 mm
Shipping Weight (Calculated) 4.5 kg

Connections and Interfaces

Terminal Designation Circuit / Function Assignment
R/L1, S/L2, T/L3 Main Three-Phase AC Power Input Connection
U, V, W Three-Phase Variable Frequency Output to Motor
P/+, PR Braking Resistor Connection Terminals
STF / STR Forward Run Start / Reverse Run Start Digital Inputs
SD Common Terminal for Digital Inputs and 24 VDC Power source
2, 4, 5 Analog Frequency Setting Inputs (Voltage / Current) & Common Ground

Alternative Models & Compatibility

The FR-A840-1.5K-1 serves as the direct technological replacement for legacy FR-A740-1.5K series drive models. While the footprint and control terminals line up similarly, please note that parameter structures have expanded. When utilizing FR Configurator2 software to import existing parameter files from A700 series models, a careful verification of acceleration-deceleration curve parameters and motor tuning maps must be performed to ensure smooth commissioning.

Application Pitfalls & Engineering Notes

During integration inside IP54 enclosed control panels, local heat dissipation must be handled correctly. The drive requires a minimum space clear-zone of 50 mm above and below the chassis for unimpeded natural airflow. In applications operating continuously at low speeds under high-torque demand, the integrated motor fan will lose efficiency. Always implement an external forced cooling fan on the motor or utilize inverter-duty rated motors to prevent winding thermal trips (E.THT faults).

Commissioning & Wiring Tips

Ensure that Parameter 79 (Operation Mode Selection) is explicitly set to match your system master. For example, setting Pr.79 to "2" locks control logic exclusively to the external terminals, bypassing the PU keypad. For RS-485 serial communication daisy chains, apply a terminating resistor on the final physical node and run standard double-shielded twisted pair (STP) control cables. The shield must be terminated strictly at a single point (PE ground at the cabinet entry) to prevent destructive ground loops.

Installation Guidelines

CRITICAL WARNING

Isolate all main power lines prior to physical cabinet mounting or control terminal wiring. Once input power is switched off, wait a minimum of 10 minutes for the internal DC bus capacitors to fully discharge. Always measure the DC bus voltage across terminals P/+ and N/- using a calibrated digital multimeter to verify the potential is below 50 VDC before initiating touch-sensitive electrical tasks.

1

Securely mount the variable speed drive on a rigid, vibration-resistant vertical panel backplate using appropriate M5 bolts.

2

Connect the physical PE protective ground terminal directly to the central cabinet earth bar before wiring power supply lines.

3

Terminate the three-phase power lines at R/L1, S/L2, and T/L3, ensuring correct phase configuration, and route the motor outputs from U, V, and W.

4

Secure control signal wiring away from the high-voltage power lines inside separate wire ducting lanes to prevent inductive cross-talk.

Loading product navigation…

What is the rated output current of the FR-A840-1.5K-1 under normal duty conditions?

The rated output current for this model is 4.0 A under Normal Duty (ND) conditions, specifically configured to drive a 1.5 kW induction motor.

Can I run this variable speed drive with a single-phase supply?

No. The drive is designed strictly for three-phase AC power input ranging from 380 to 500 VAC. Attempting to power it on a single-phase line will cause input phase failure trips.

Which communication interfaces are natively integrated into the FR-A840-1.5K-1?

The drive features integrated RS-485, RS-422, and RS-232 serial interfaces, allowing communication using Mitsubishi Electric RTU protocols or standard Modbus RTU.

What is the recommended environmental temperature limit for operating this VFD?

The drive operates reliably at ambient temperatures between -10 degC and +50 degC under non-freezing conditions. Derating is required for ambient temperatures above 50 degC.

Expédition express mondiale

  • Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
  • Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
  • Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats arabes unis.

Retours et garantie

  • Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d'origine scellé en usine.
  • Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.

Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).


Pour connaître l'éligibilité complète, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel Politique de remboursement et de retour .

TECHNICAL SPECIFICATIONS

Country of origin
États-Unis

Produits récemment consultés

Connaissances techniques

Actionneurs électriques conçus pour remplacer les systèmes à fluide : un guide pratique d'automatisation industrielle

Cet article explique comment les actionneurs électriques intégrés, tels que la série e-Actuator de SMC, transforment le contrôle du mouvement industriel en remplaçant les systèmes pneumatiques et...

Opérations mathématiques avec OpenPLC pour les applications d'automatisation industrielle

Cet article explique comment les systèmes PLC réalisent des opérations mathématiques de base telles que l'addition, la soustraction, la multiplication, la division, le modulo et l'exponentiation dans...

Logique booléenne avancée avec la programmation FBD PLC : applications industrielles pratiques au-delà de la logique de base

L'article explique plusieurs fonctions avancées de la logique booléenne utilisées en programmation d'automates programmables industriels (API) au-delà des opérations de base ET, OU et NON. Il aborde...

Logique booléenne en programmation PLC : comprendre les portes logiques FBD

La logique booléenne est la base de tout programme PLC. Des commandes machines simples aux systèmes d'automatisation industrielle complexes, les portes logiques déterminent comment les contrôleurs...

Guide approfondi sur les pare-feux industriels et la segmentation des réseaux OT

Les pare-feux industriels jouent un rôle crucial dans la cybersécurité OT, protégeant les réseaux PLC, DCS et SCADA grâce à la segmentation, au contrôle des entrées/sorties et à l’intégration IDS/IPS...

Guide des pinces robotiques : de la manipulation délicate à l'automatisation lourde

Les pinces robotiques modernes évoluent au-delà des mâchoires mécaniques traditionnelles. Des systèmes adhésifs inspirés des geckos aux pinces souples de qualité alimentaire, en passant par des...